Fire-resistance rating requirement for building elements: (T-601)
Type V-B,
Any materials permitted (602.5)
Windows(T-715.5)
Door&Shutter(T-715.3)
Structural frame
0
hours
a
Exterior bearing walls
0
hours
f
0
hours
#N/A
hours
Interior bearing walls
0
hours
0
Floor construction
0
hours
0
Roof construction
0
hours
0
Int. Non-bearing & partition
NR
Fire-resistance rating requirements for exterior walls based on fire separation distance. (T-602)*
For Type V-B,Group R-3
Ext Wall Setback (ft)
Fire Rating
hrs
hrs
hrs
Unprotected
Protected
North
5.1
1
¾
¾
10
a,c,e,g,h,i
25
a,c,e,g,h,i
1
South
4.5
1
¾
¾
NP
a,c,g
15
a,c,g
1
West
10
0
0
0
NL (g)
a,c,e,g,h,i
NL (g)
a,c,e,g,h,i
0
East
30
0
0
0
NL (g)
a,d,g,i
NL (g)
a,d,g,b
0
*For special requirements for Group U occupancies see Section 406.12
Required Separation of Occupancies (T-508.3.3)*
Between
=
2
hours, NS
c, d
b
1
hours, S
S = Buildings equipped throughout with an automatic sprinkler system installed in accordance withSection 903.3.1.1.
NS = Buildings not equipped throughout with an automatic sprinkler system installed in accordance withSection 903.3.1.1.
Fire wall fire resistance rating, considered a separate building. (T-705.4 )
Occupancies Group
1
Type of construction
8
Required fire resistance rating
2
hours
Shaft enclosures (if required per 707.2)
fire resistance rating
1
hours
Opening protective fire rating for fire door and shutter assemblies (715.4)
Type of Assembly
Rating
Minimum Opening Protection
7
2
⅓
hours
The required locations for fire and smoke dampers: (716.5)
Fire Damper
Smoke Damper
Location
Section
Nonspr Sprinkler
Nonspr Sprinkler
1
302.1.1.1
Yes (1)
Yes (1)
No
No
Group
R-3
SPRINKLERED
UNSPRINKLERED
C
C
Exit access corridors & other exitways
C
C
C
C
Fire Alarm and Detection Systems (907)
Occupancy
Section System Type
5
907.2.3
Manual fire alarm system
Exception:
Manual fire alarm boxes not required where six specific condition are met.
Group R-3, An automatic sprinkler system shall be provided where:
0
Type of construction V-B
Class
C(c)
Roof covering
Windows
(715.5)
(715.3)
Doors
Max area of opening in percentage of the
area of exterior wall.T-704.8
Interior wall and ceiling finish requirement by occupancy T-803.5
kVertical exit & exit passageways
a bRoom & enclosed space
cMinimum roof covering classification for type of construction T-1505.1
a b&
S-2
M
A-1
V-A
1
Smoke barriers
Incidental Uses (FB)
E, Occupant load 50
MINIMUM NUMBER OF REQUIRED PLUMBING FACILITIES PER T-2902.1
Water Closets
UBC 1997
Occupancy Factor = 30
sq. ft per occupant
water closet
A
M
Total Area
=
48,000
Sq. ft
Total Occupant
= 1,600
Required water closet
##
Male:
=
8
A
Female:
=
9
A
A
Required lavatories
A
Male:
=
6
B
Female:
=
7
B
Required bath or shower
E
Total:
0
=
0
E
Required drinking fountain
E
Total:
1 per 150
=
11
E
Conference rooms, dining rooms, drinking establishments,
exhibit rooms, gymnasiums, lounges, stages and similar
uses including restaurants classifies as group B
Occupancies.
1:1-25, 2:26-75, 3:76-125,
4:126-200, 5:201-300,
6:301-400, over 6:301-400, add one for
each additional 200
1:1-25, 2:26-75, 3:76-125,
4:126-200, 5:201-300,
6:301-400, over 6:301-400, add one for
each additional 150
1 for each water closet up to 4,
then 1 for each two additional
water closets
1 for each water closet up to 4,
then 1 for each two additional
water closets
MINIMUM NUMBER OF REQUIRED PLUMBING FACILITIES PER T-2902.1
IBC 2003
E
Educational facilities
Total Occupant
=
15
Required water closet
Male:
1 per 50
=
1
Female:
1 per 50
=
Separate ficilities shall not be required
Required lavatories
Male:
1 per 50
=
1
Female:
1 per 50
=
Separate ficilities shall not be required
Required bath or shower
Total:
0
=
0
Required drinking fountain
Total:
1 per 100
=
1
Other
1 Service sink
Means of Egress,
CHAPTER 10
Floor Area
Use
Area 1
5,000
240 gross
21
1
Area 2
500
35 net
15
2
0 0
0 0
0 0
0 0
0 0
0 0
0 0
Other
200
Total occupant load
36
1
No.of exits required
2
Egress width (Inches) per occupant served, Table 1005.1
Occupant Occupancy
Without sprinkler system
With sprinkler system
Load
Group
Stair way
Other Egress
Stair way
Other Egress
0.3
0.2
0.2
0.15
15
5 (in)
3 (in)
3 (in)
3 (in)
Panic and fire exit hardware
Not required
Travel Distance, Table 1015.1
For Group R-2
Without sprinkler system
200
feet
With sprinkler system
250
feet
a,b
Common path of egress travel.1014.3
75
feet
125 feet, with sprinkler
Corridor fire-resistance rating, Table 1017.1
For Group R-2
Without sprinkler system
NP
hrs
With sprinkler system
½
hrs
c
When occupant load served by corridor
> 10
Building with 1 exit, Section 1019.2
Occupancy
Max story ht.
R-2
1 story
10 occupants and 75 feet travel distance
or
2 story
Occupancy
Group
Floor area per
occupant
T-1003.2.2.2
Occupant
Loads
No of
Exit
1004.2.1
Max occupants (or dwelling units) per floor and
travel distance
4 dwelling units occupants and 50 feet travel
distance
Inpatient treatment areas
I-2
Day care
I-4
Description
Required water closet
Required lavatories
Male:
Female:
Male:
Female:
Total:
Total:
Other
A-2
1 per 75 1 per 75 1 per 200 1 per 200
0
1 per 5001 Service sink
100
1
1
1
1
0
1
0
00
0 0 0 00
00
0
0
0
0
0
0
0
0
00
0 0 0 00
00
0
0
0
0
0
0
0
0
00
0 0 0 00
00
0
0
0
0
0
0
0
0
00
0 0 0 00
00
0
0
0
0
0
0
0
Total Occupants =
100
1
1
1
1
0
1
MINIMUM NUMBER OF REQUIRED PLUMBING FACILITIES PER T-2902.1
Used
Group
Required bath
or shower
Required drinking
fountain
Restaurants, banquet halls and
Description
Required water closet
Required lavatories
Male:
Female:
Male:
Female:
Total:
Total:
Other
A-2
Casino0
1 per 5001 Service sink
901
4
9
3
3
0
2
0
00
0 0 0 00
00
0
0
0
0
0
0
0
0
00
0 0 0 00
00
0
0
0
0
0
0
0
0
00
0 0 0 00
00
0
0
0
0
0
0
0
0
00
0 0 0 00
00
0
0
0
0
0
0
0
Total Occupants =
901
4
9
3
3
0
2
Used
Group
Required bath
or shower
Required drinking
fountain
No. of
Occupants
1:1-100, 2:101-200, 3:201-400. Over 400, add one fixture each additional 250.
3:1-50, 4:51-100, 6:101-200, 8:201-400 Over 8:201-400, add one fixture each additional 150.
1:1-200, 2:201-400, 3:401-750, Over 750, add one fixture for each additional 500
1:1-200, 2:201-400, 3:401-750, Over 750, add one fixture for each additional 500
MINIMUM NUMBER OF REQUIRED PLUMBING FACILITIES PER T-2902.1
with SNBC amendments.
Lighting Application Worksheet
2006 IECC (SNBO)
PROJECT:
Name
Section 1: Allowed Lighting Power Calculation
Building Type
Allowed Watts
Auditorium
1.8
2000
14 ft
1.10
3960
Total Area =
2000
Total Allowed Watts =
3960.0
Section 2: Actual Lighting Power Calculation
LAMP TYPE
Fixture ID
Lamps/ Fixture # of Fixtures
Total Watts
48" T8 25W (Super T8)
A
3
15
20
300
0
0
0
0
0
0
0
0
0
Incandescent 250
0
Total Actual Watts =
300
Section 3: Compliance Calculation
Total Allowed Watts =
3,960
Total Actual Watts =
300
Project Compliance =
3,660
Lighting PASSES: Design 92 % better than code
LPD
(T-505.5.2)
Floor Area ft
2Adjust for
Heights
above the
floor
Fixture
Watt
1607.11.2 MINIMUM ROOF LOAD
300.0 SQ.FT ##
1.2-.001At Eq. 16-29 ##
= 0.90 Eq. 16-28
Rise per feet, F = 4:12 ##
1.00 Eq. 16-31 ##
= 1.00 Eq. 16-31
Eq. 16-24
= 20(0.9)(1) Interior columns
18.00 psf Exterior columns without cantilever slabs 44
1607.9 REDUCTION OF LIVE LOAD Edge columns with cantilever slabs 3
1607.9.1 General Corner columns with cantilever slabs
L = (6-24) Edge beams without cantilever slabs
40 psf T-1607.1 Interior beams
1 T-1607.9.1 Edge beams with cantilever slabs
2000.0 SQ.FT Cantilever beams
L =23.4 psf = 0.59 Two-way slabs
Members without provisions for continuous shear transfer normal to their span 1607.9.2 Alternate Live Load reduction for
40 psf ##
R = r(A-150) (16-25) Horizontal member
A = 2000.0 SQ.FT Vertical member
r = 0.08 for floor
R = 60 60% Max for vertical member
L = 16 psf
And R = (16-26)
Dead load D =75.0 psf
R = 60.0 60% Max for vertical member
L = 16.0 psf
Min Design Live Load L =16.0 psf
(7-1) ##
100 psf Figure 7-1 Is
Terrain Category = B (see Section 6.5.6)
Exposure of Roof = C (see Section 6.5.6)
Thermal Condition = D (see Section 6.5.6)
1 Table 7-4 Above the treeline in windswept mountainous areas
0.7 Table 7-2 In Alaska, in areas where trees do not exist within a 2-mile radius of the site
1.1 Table 7-3 ##
53.9 psf All structures except as indicated below
20 psf 7.3 Structures kept just above freezing and others with cold, ventilated roofs in which the thermal resistance (R-value) 1.1 between the ventilated space and the heated space exceeds 25 ft2¥hr¥¡F/Btu
53.90 psf Unheated structures
Continuously heated greenhouses with a roof having a thermal resistance (R-value) less than 2.0 ft2¥hr¥¡F/Btu (7-2)
53.90 psf ##
Slope Θ =25 Unobstructed Slippery Surfaces
1.1 All Other Surfaces
0.75 7.4.1, 7.4.2, 7.4.3 Figure 7.2a,b and c ###
40.43 psf W =15.00ft ##
Balanced and Unbalanced Snow Load for Hip and Gable Roof #
Snow Density γ = (7-3) # = 27.00 pcf # S =1/tanΘ = 2.14 Θ = 25 # =1 ft = 18.44 psf Θ > = 3.91 ft 40.43ft Θ ≤
See Figure 7.3 for Curved Roof BALANCED ###
See Figure 7.4 for Cont Beam ###
See Figure 7-6 for Sawtooth Roof 100.00ft W ≤ 20
See Figure 7-8 for Snow Drifts UNBALANCED W ≤ 20 W > 20
3.91ft 18.44psf UNBALANCED OTHER 12.13ft 40.43ft Tributary area At = R1 = R2 = Lr = 20R1R2
Min Design Roof Load Lr =
Lo[0.25+15/(KLLAT)]1/2
Lo =
KLL =
AT =
Lo
L shall not be less than 0.50Lo for members supporting one floor and L shall not be less
than 0.40Lo for members supporting two or more floors
Lo =
23.1(1+D/Lo)
ASCE 7.3 FLAT ROOF SNOW LOAD (slope ≤ 5o ) Flat-roof snow load, pf = 0.7CeCtIspg Ground snow load, pg =
Snow load importance factor, Is = Snow exposure factor, Ce = Thermal factor, Ct = Flat-roof snow load, pf =
Min pf = Design pf =
7.4 SLOPE ROOF SNOW LOAD (slope > 5o ) ps = Cspf Design pf = o Ct = Slope factor Cs = ps = .13pg + 14 ≤ 30 pcf
Height of Snow Drift hd hdγ/S½ 8/ 3hdS½ ps = ps =
Cantilever beams
Vertical member
Above the treeline in windswept mountainous areas
Fully Exposed
Structures kept just above freezing and others with cold, ventilated roofs in which the thermal resistance (R-value) 1.1 between the ventilated space and the heated space exceeds 25 ft2¥hr¥¡F/Btu
IBC2006 (1613), ASCE 7-05 CHAPTER 11, 12, 13 SEISMIC DESIGN CRITERIA
175.00%g
= 1.750g
Figure 22-1 through 22-14
75.00%g
= 0.750g
Soil Site Class
Table 20-3-1, Default = D
1.000
Table 11.4-1
1.500
Table 11.4-2
= 1.750
(11.4-1)
= 1.125
(11.4-2)
= 1.167
(11.4-3)
= 0.750
(11.4-4)
Building Occupancy Categories
Table 1-1
Design Category Consideration:
with dist. between seismic resisting system >40ft
Seismic Design Category for 0.1sec
D
Table 11.6-1
Seismic Design Category for 1.0sec
D
Table 11.6-2
S1 ≥ .75g
E
Section 11.6
Since Ta < .8Ts (see below), SDC =
E
Comply with Seismic Design Category E
D2
12.8 Equivalent lateral force procedure
A. BEARING WALL SYSTEMS
Seismic Force Resisting Systems
0.02
x = 0.75
T-12.8-2
20
ft
Limited Building Height (ft) =
NP
1.400
0.750g Table 12.8-1
= 0.189
.266 Sec
Cu.Ta
= 0.265
Use T = 0.265
sec.
0.8Ts =
= 0.600
Is structure Regular & ≤ 5 stories ?
12.8.1.3
1.500g
Max Ss ≤ 1.5g
1.00
= 1.000g
(11.4-3)
Response Modification Coef. R =
2
Table-12.2-1
2
foot note g
1
Table 11.5-1
Seismic Base Shear V =
=0.583
(12.8-2)
R/I
= 1.416
(12.8-3)
N/A
(12.8-4)
0.01
(12.8-5)
= 0.188
(12.8-6)
0.583
Design base shear V =
0.583 W
Control
12.14 Simplified Seismic base shear
1.167
SDC = E
Limitations:
NP
F =
1.1
For two-story building
R = 4
V =
= 0.321 W
R
13.3 Seismic Demands on Nonstructural Components
(13.3-1)
1.167
1
3
T-13.5-1 or 13.6-1
1.0
13.1.3
z =
10 ft
h =
10 ft
0.467 Wp
= 1.867Wp
(13.3-2)
= 0.350Wp
(13.3-3)
0.467 Wp
12.11.1 Structural Walls and Their Anchorage
12.11.1
=
0.467(W)
= 467
(12.11.1)
=
0.933 Wp
(12.4.4), (12.4.5), (12.4,6), (12.4.7)
2
0.234(D)
1.75
Nonbuilding structures, Section 15
Response Modification Coef. R =
3
T-15.4-1 or T-15.4-2
1
15.4.1.1
= 0.389
0.03
(15.4-1)
= 0.200
(15.4-2)
V =
0.389 W
(15.4-5)
= 0.300 W
Response Spectral Acc. (0.2 sec) Ss =
Response Spectral Acc.( 1.0 sec) S
1=
Figure 22-1 through 22-14
Site Coefficient F
a=
Site Coefficient F
v=
Max Considered Earthquake Acc. S
MS= F
a.S
sMax Considered Earthquake Acc. S
M1= F
v.S
1@ 5% Damped Design S
DS= 2/3(S
MS)
S
D1=
2/3(S
M1)
IRC, Seismic Design Category =
C
t=
Building ht. H
n=
C
u=
for S
D1of
Approx Fundamental period, T
a= C
t(h
n)
x12.8-7 T
L
=
Calculated T shall not exceed ≤
0.8(S
D1/S
DS)Response Spectral Acc.( 0.2 sec) S
s=
F
a=
@ 5% Damped Design S
DS=
⅔
(F
a.S
s)
Over Strength Factor
Importance factor I =
C
sW
C
s=
S
DSor need not to exceed, C
s=
S
D1For T≤ T
L
(R/I).T
or C
s=
S
D1T
LFor T > T
LT
2(R/I)
C
sshall not be less than =
Min C
s=
0.5S
1I/R
For S
1≥ 0.6g
Use C
s=
@ 5% Damped Design S
DS=
FS
DS(W)
F
p= 0.4a
pS
DSW
p(1+2z/h)
S
DS=
(R
p/I
p)
a
p=
R
p=
I
p=
F
p=
Max F
p=
1.6S
DSI
pW
pMin F
p=
0.3S
DSI
pW
pF
p=
F
p= 0.40S
DSIW
w12.11.2 Anchorage of Concrete or Masonry structural Walls (flexible diaphragm)
or F
p= 400S
DSI
shall be ≥ 280 #/ft
F
p= 0.8S
DSI(W
w)
Max Seismic Load E
M=
Q
E± 0.2S
DSD
Where
=
0.2S
DSD =
Deflection Amplification factor C
d=
Importance factor I =
For flexible nonbuilding, C
s= S
DSI/R
Min C
s=
or C
s= 0.8 S
1I/R
For rigid nonbuilding, C
s= 0.3 S
DSI
T-12.14-1 T-12.2-1 T-R301.2.2.1.1
D
II, Standard
Flexible Diaphragm
9. Ordinary reinforced masonry shear walls
0.265
Yes
ASCE 7-05 (IBC 2006) WIND: BUILDING DATA:
Basic wind speed (3 sec gust) =
90
MPH
Exposure
Roof Pitch =
4.00
:12
Mean Roof Height h =
25
ft
1.00
T-6-1
6.4 METHOD 1- SIMPLIFIED PROCEDURE (LOW-RISE, 60 FT)
1.00
Fig 6-2
-10.70G
-7.97H
-10.70G
-6.80H
-15.40E
-10.51F
-15.40E
-8.80F
-2.73D
-4.92B
θ=
18.4
11.52C
8.50C
H =27.4
17.27A
All forces shown in psf
22.58333
12.80A
29
49
TRANSVERSE ELEV.
LONGITUDINAL ELEV.
12.80A
2a= 6.0ft
10 % of least dimension=
2.9 ft
13.53 kips
40 % of the eave height =
9.0 ft
29 ft
6.77 k
10.1psf
4 % of least dimension or 3 ft=
3.0 ft
8.50C
9.3 psf
therefore a =
3.0 ft
49 ft
(6-1)
All forces shown in psf
6.0ft
1.00
6.5.7
12.8
Fig 6-2
11.52C
17.27A
Height Adjustment factor λ =
1.00
Fig 6-2
PLAN VIEW
Importance factor Iw =
1.00
6.2
FIGURE 6.2, Main Wind Force System
12.80psf
MWFRS
Horizontal Loads
Vertical Loads
Load
Roof
End Zone
Interior zone
End Zone
Interior zone
Overhang
Direction
Angle Wall (A) Roof (B) Wall (C ) Roof (D)
WW (E)
LW (F) WW (G) LW (H)
Transverse
18.4
17.27
-4.92
11.52
-2.73
-15.40
-10.51
-10.70
-7.97
-21.60
-16.90
Longitudinal
All
12.8
-6.7
8.5
-4
-15.4
-8.8
-10.7
-6.8
-21.6
-16.9
* If roof pressure under horizontal loads is less than zero, use zero
Plus and minus signs signify pressures acting toward and away from projected surfaces, respectively.
FIGURE 6-3, COMPONENT AND CLADDING
Roof effective area =
30
18.4
Effective Area for wall element =
20
Sq. ft
Interior Zone 1 = 9.45
-12.87 psf
Wall, Interior Zone 4 = 13.90
-15.10 psf
End Zone 2 = 9.45
-17.98 psf
End Zone 5 = 13.90
-18.20 psf
Conner Zone 3 = 9.45
-23.90 psf
Roof Overhang effective area =
6
sq. ft
Interior Zone 2 = -26.13
psf
End Zone 3 = -36.71
psf
IBC 1605.2.1(LRFD) U = 0.9D + 1.6W
IBC 1605.3.1(ASD), U = 06D + W, increase in allowable shall not be used.
IBC 1605.3.2(ASD), U = D + 1.3 W, allowable stress are permit to be increased.
Importance factor I
w=
Height Adjustment factor λ =
Example: p
s= λ K
ztIp
s30K
zt=
horizontal load at end zone p
s30=
E
OHG
OHFor the design of the longitudinal MWFRS use Ө = 0°, and locate the zone E/F, G/H boundary at the mid-length of the building
sq. ft,
=
=
=
X
X
ASCE7-05, 6.5.7 Topographic Effects
x =
50
H =
80
= H/2
320
Height above local ground z =
45
ft
Hill Shape
Direction
Exposure
B
Height of hill, H=
80 ft
##
320 ft
2-dimensional ridge
0.25
2-dimensional escarpments
0.25
3-dimentional axisym
Distance from the crest to the building, x =
50 ft
0.16
0.95
0.24
320
µ =
1.5
0.90
γ =
4
0.57
(6-3)
1.26
L
h=
Distance upwind of crest to where the
difference in ground elevation is half the
height of hill, L
h=
H/L
n=
calculate K
1by using H/L
n=
x/L
h=
Figure 6-4, K
1/(H/L
h) =
K
1=
calculate K
2, K
3by using L
n=
K
2= 1 - x/µL
hK
2=
K
3 = e-γz/LhK
3=
K
zt= [1 +K
1K
2K
3]
2K
zt=
Back to Wind load
3-dimentional axisym
Downwind of Crest
6.5.14 Design Wind Load on Solid Freestanding Walls and Solid Signs Per ASCE 7-05 F = (6-27) B =20.00 (6-15) Exposure 1.4 1.00 (6.5.7.2) s = 10.00 0.85 (6.5.4.4) 0 to s s to 2s Wind Speed V=90 Impotance factor I=0.87 (6.5.5), T-6-1 15.33 0.85 (6.5.8) 0.00 ft 1.00 ft Balance B/s= 2.00 Cf =1.40 s/h = 1.00 1.40 Fig 6-20
Since B/s ≥ 2 Case C must also be considered
Total # of Segment with width = s Vert. location of resultant force 0.00 ft 1.50 ft
= 2 5.5 ft from grade
Balance, see Fig 6-20 = 0.00 ft Total h =10.00
0 to s, = 2.25 s to 2s, = 1.50
0.00 ft 2.00 ft
Case C, Multiples factor (if applicable)
0.0 ft Free Standing Wall, Case B= 10.40PSF when s/h > 0.8, (1.8-s/h) = 0.80 Free Standing Wall, Case C= 11.14PSF
for Lr/s = 0.00, = 1.00 1 0.9 %openning =0.0% Reduction factor = 1.00 d = 6.77 ft Method A & B Sign h F (lbs) M (ft-lbs) 10.00 200.0 1.40 0.57 8.7 2080.2 11441.4 Pole 0.00 0.0 1.2 0.57 8.7 0.0 0.0 0.00 0.0 1.2 0.57 8.7 0.0 0.0 3.00ft 0.00 0.0 1.2 0.57 8.7 0.0 0.0 Total 2,080.2 11,441.4 H = 5.50 ft Method C Sign h F (lbs) M (ft-lbs) PSF
Balance, see Fig 6-20 = 10.00 0.00 1.40 0.57 8.7 0.0 0.0
0 to s, = 10.00 100.00 2.25 0.57 8.7 1337.3 6686.5 13.37 s to 2s, = 10.00 100.00 1.50 0.57 8.7 891.5 4457.7 8.92 0.57 8.7 0.0 0.0 0.57 8.7 0.0 0.0 0.57 8.7 0.0 0.0 0.57 8.7 0.0 0.0 0.57 8.7 0.0 0.0 Pole 0.00 0.0 1.2 0.57 8.7 0.0 0.0 0.00 0.0 1.2 0.57 8.7 0.0 0.0 0.00 0.0 1.2 0.57 8.7 0.0 0.0 Total 2,228.8 11,144.2 H = 5.00ft IBC 1805.7: Design Employing Lateral Load Bearing
Total Lateral Load, P = 2080.2lbs Dist from ground to point of P, H = 5.50ft *Allowable lateral soil-bearing, S = 100.00lbs/sq ft/ft
Allowable Increase = 2 x100.00 lbs/sq ft/ft Dia of footing or diagonal of sq. footing, b = 3.00ft
Constrained at ground = No S1 = 866 lbs/sq ft ≤ 15 x 100 O.K. = 2.34P/S1 b d = 0.5A[1+(1+(4.36h/A))½] d = 6.77 ft qh G Cf As qz= .00256 Kz Kzt Kd V2 I Exposure coefficient Kz = Topography factor Kzt = Directionality factor Kd = qz= Kz
Gust Effect factor G = L1 = D1 =
Case A & B, Cf =
L2 = D2 =
Case C, Cf for Region
L3 = D3 =
Horizontal dim of return corner Lr =
area As Cf Kz qh
area As Cf Kz qh
Design Requirement by Category Category A Category B Category C Category D Category E Category F
For: 9. Ordinary reinforced masonry shear walls, see 14.4
Limit Building Height Table-12.2-1 NL NL 160 NP NP NP
Seismic load effect E, 12.4
25 % Increase in Force for Connection
Horizontal Irregular 1a,1b,2,3 or 4 1a,1b,2,3 or 4 1a,1b,2,3 or 4
Vertical Irregular 4 4 4
Anchorage of concrete or masonry walls
Flexible
1 1 1 1.3 1.3 1.3
min
Collector element & connection, 12.10.2 Light frame
Structural Walls and Their Anchorage, 12.11.1
min 0.1Ww
Element Supporting discontinuous Wall and Frame, 12.3.3.3
Horizontal Irregular Not Permit na na na na 1b 1b
Vertical Irregular Not Permit, 12.3.3.1 na na na 5b 1b, 5a or 5b 1b, 5a or 5b Extrem Weak Stories 12.3.3.2 5b not over 2-story 5b not over 2-story 5b not over 2-story
Building Separations, 12.12.3 y y y y y y
Concrete
Seismic-force-resisting systems IBC 1908.1 IBC 1908.1.4 IBC 19081.4 IBC 1908.1.4 IBC 1908.1.4 Discontinuous members. IBC 1908.1.12 IBC 1908.1.12 IBC 1908.1.12 IBC 1908.1.12
Plain IBC 1910.4.4 IBC 1910.4.4 IBC 1910.4.4 IBC 1910.4.4
n/a n/a n/a IBC 1910.5.2 IBC 1910.5.2 IBC 1910.5.2
Slab on Grade IBC1911.1 IBC1911.1 IBC1911.1 IBC1911.1 IBC1911.1
Masonry IBC 2106.3 IBC 2106.4 IBC 2106.5 IBC 2106.6 IBC 2106.6
Seismic Design Requirement MSJC 1.14.3 MSJC 1.14.4 MSJC 1.15.5 MSJC 1.14.6 MSJC 1.14.7 MSJC 1.14.7
Wall not part of the lateral-force-resisting system IBC 2106.3.1 IBC 2106.3.1 IBC 2106.3.1 IBC 2106.3.1 IBC 2106.3.1
IBC 2106.4.1 IBC 2106.4.1 IBC 2106.4.1 IBC 2106.4.1
1.5 times the forces IBC 2106.5.1 IBC 2106.5.1 IBC 2106.5.1
Steel, AISC 341
Structural steel IBC 2205.2.1 IBC 2205.2.1 IBC 2205.2.1 IBC 2205.2.2 IBC 2205.2.2 IBC 2205.2.2
Composite IBC 2205.3 IBC 2205.3.1 IBC 2205.3.1 IBC 2205.3.1
Light frame IBC 2210.5 IBC 2210.5 IBC 2210.5 IBC 2210.5 IBC 2210.5 IBC 2210.5
Wood
General IBC 2305 IBC2305 IBC2305 IBC2305 IBC2305 IBC2305
Shear wall 2305
Structural wood panel, h/d ratio, 2305.3.3 2:1 2:1 2:1
Gypsum Board & Stucco NP NP
Particleboard NP NP NP
Fiberboard NP NP NP
Shear panel connections (2305.1.4)
NA NA NA IBC 2305.1.4 IBC 2305.1.4 IBC 2305.1.4Sill Plate IBC 2305.3.11 IBC 2305.3.11 IBC 2305.3.11
MSJC = Masonry Standards Joint Committee (ACI 530.1-05/ASCE 6-05/TMS 602-05)
QE ± 0.2DDSD QE ± 0.2DDSD QE ± 0.2DDSD QE ± 0.2SDSD QE ± 0.2SDSD QE ± 0.2SDSD 0.40SDSIWw 0.40SDSIWw 0.40SDSIWw 0.40SDSIWw 0.40SDSIWw 0.40SDSIWw 400SDSI 400SDSI 400SDSI 400SDSI 400SDSI 400SDSI 0.8SDSIE(Ww) 0.8SDSIE(Ww) 0.8SDSIE(Ww) 0.8SDSIE(Ww) 0.8SDSIE(Ww) Redundancy, Diaphragm, 12.10 max 0.4SDSIwpx 0.4SDSIwpx 0.4SDSIwpx 0.4SDSIwpx 0.4SDSIwpx 0.4SDSIwpx 0.2SDSIwpx 0.2SDSIwpx 0.2SDSIwpx 0.2SDSIwpx 0.2SDSIwpx 0.2SDSIwpx QE QE Em=QE ± 0.2SDSD Em=QE ± 0.2SDSD Em=QE ± 0.2SDSD Em=QE ± 0.2SDSD QE QE QE QE QE QE
.40IESDSWw .40IESDSWw .40IESDSWw .40ISDSWw .40IESDSWw .40IESDSWw
0.1Ww 0.1Ww 0.1Ww 0.1Ww 0.1Ww
Em=QE ± 0.2SDSD Em=QE ± 0.2SDSD Em=QE ± 0.2SDSD Em=QE ± 0.2SDSD Em=QE ± 0.2SDSD
Frame members not proportioned to resist forces induced by earthquake motions.
Design of discontinuous members that are part of the lateral-force-resisting system
31/ 2:1 3 1/ 2:1 3 1/ 2:1 11/ 2:1 11/2:1 11/2:1 11/2:1 31/ 2:1 31/2:1 31/2:1 11/ 2:1 11/2:1 11/2:1
CONCRETE SLENDER WALL PER IBC-2006, ACI 318-05,Section 14.8 Ver 4/2006
4500psi E = 12.4.2.3
60000psi = 0.23 D
Wind Load, W = 14psf Load Combination, IBC 1605.2.1
0.467 U = 1.20 D + 1.6L (16-3)
1.17g U = 1.20 D + 0.5L + 1.6W (16-4)
27ft U = 1.43 (16-5)
Parapet Height, p = 0ft U = 0.90 D + 1.6W (16-6)
Eccentric, e = 2.7in U = 0.67 (16-7)
Design width, b = 24in Concrete wt. = 150pcf
Effective thickness, t = 6in h/t = 54.0 Design, d = 3.8in n = 7.1 75.0 psf 4,066,840 psi 0.9 0.825 Dead Load, D = 200plf Live Load, L = 100plf Vertical Rebars = # 5 Spacing = 24in Horizontal rebars = # 5 Spacing = 24in
2025 lbs Load Combination For Strength Design:
(16-3) (16-4) (16-5) (16-6) (16-7)
800.0 580.0 673.3 360.0 266.7 lbs 2430.0 2430.0 2902.5 1822.5 1350.0 lbs = 3230.0 3010.0 3575.8 2182.5 1616.7 lbs
Max 24.8 ≤ 0.06f'c, OK, 14.8.2.6 = 22.4 20.9 24.8 15.2 11.2 psi
= 44.8 70.0 44.8 70.0 plf 0.310 sq.in ≤ OK (14.8.2.3) = 0.36 0.36 0.37 0.35 0.34 sq.in a = = 0.24 0.24 0.24 0.23 0.22 inch c = a/0.85 = 0.28 0.28 0.28 0.27 0.26 inch (0.003/c)d - 0.003 = 0.038 0.038 0.037 0.040 0.041
≥ 0.005 for tension conctrol OK OK OK OK OK
= 80,358 79,574 81,590 76,621 74,597 lb-in
(14-7) = 32.33 32.05 32.76 30.99 30.26
= 1,080 49,772 77,454 49,475 76,905 lb-in (14-4) = 1,683 75,038 127,236 66,184 95,122 lb-in
(14-5) = 0.19 8.39 13.92 7.66 11.27 in
Strength check 72,323 71,617 73,431 68,959 67,138 lb-in
(14-3) OK NG NG OK NG
Deflection at service load Load combination = D + L +(W or 0.7E) (16-15)
Seismic Wind 600.0 600.0 lbs 2,025.0 2,025.0 lbs 2,625.0 2,625.0 lbs w = 49.0 28 plf = 432 432 (9-9) = 72,449 72,449 lb-in > øMn, NG (14-2) = 0.45 0.45 in a = = 0.20 0.20 in c = a/0.85 = 0.24 0.24 in (14-7) = 28.15 28.15 (14-10) = 55,295 31,950 lb-in (9-8) = 432.0 432.0 (14-9) = 0.34 0.20 inch 14.8.4 = 2.16 2.16 inch
Check total reinforcement OK OK `
Vertical reinforcement = 0.0022 Horizontal reinforcement = 0.0022 Total = 0.0043
Compressive strength, f'c = QE ± 0.2SDSD
Yield strength of rebars, fy = QE ±
Seismic Load QE = Fp = Wp Design response spectrum, SDS =
Wall unsupported height, lc = D + 0.5L + 1.QE
D + 1.QE
Weight of the wall, Wp = Ec =
Reduction factor, β1=
Wt. of the wall @ mid height Pw = Factored load from trib Floor/Roof , Puf = Factored weight of wall @ mid Ht, Puw =
Factored axial load, Pu = Puf+Puw Pu/Ag =
Factored distributed lateral load, wu =
As = 0.6b(b.d)
Ase = (Pu+As.fy)/fy (Pu+As.fy)/(0.85.f'c.b)
ε1 =
Nominal strength, Mn = (Asefy)(d - a/2)
Icr = n.Ase.(d-c)2+bc3/3 in4 Mua = wu.lc2/8+Puf. e
/
2 Mu obtained by iteration of deflection ∆u (10times) Mu = Mua + PuΔu u = (5.Mu.h2)/[.75(48.Ec.Icr)]Mn shall not be less than Mu Mn =
Mn > Mu
Unfactored Load trib from floor/roof, Pf = Pw = Ps = Pf + Pw Ig = b.t3/12 in4 Mcr = 7.5(f'c)1/2.I g)/0.5.t cr = (5.Mcr.h2)/(48.Ec.Ic) As.fy/(0.85.f'c.b) Icr = n.As.(d-c)2+bc3/3 in4 M = w.lc2/8+Pf.e/2+(Ps).s Ie = (Mcr/M)3Ig + [1+(Mcr/M)3]Icr ≤ Ig in4 s = (5.M.lc2)/(48.Ec.Ie) Allowable= lc/150 Ag Ag Ag
MASONRY SLENDER WALL PER IBC-2006, MSJC-05, SECTION 3.3.5 Ver 5/2003 ###
1500psi E = 12.4.2.3 #
60000psi = 0.23 D Load Combination
Wind Load, W = 5psf Load Combination, IBC 1605.2.1 .2SDS
0.224 U = 1.20 D + 1.6L (16-3) ###
1.17g U = 1.20 D + 0.5L + 1.6W (16-4) ###
Wall unsupported height, h = 35ft U = 1.43 (16-5) ###
Parapet Height, p = 0ft U = 0.90 D + 1.6W (16-6) ###
Eccentric, e = 7.3in U = 0.67 (16-7) ###
Design width, b = 12in ###
Effective thickness, t = 7.63in h/t = 55.0 #
Design, d = 3.81in n = 27.6 #
80psf 700 For clay masonry #
0.9 MSJC 3.1.4.1 = 1,050,000 psi MSJC 1.8.2 #
Tributary Dead Load, D = 50plf 84.0psi, per T-3.1.8.2.1 #
Tributary Live Load, L = 0plf #
Vertical Rebars # 5 ###
Spacing = 24in ###
Horizontal rebars # 4
Spacing = 24in
1400 lbs Load Combination For Strength Design:
(16-3) (16-4) (16-5) (16-6) (16-7) ### 60.0 60.0 71.7 45.0 33.3 lbs 1680.0 1680.0 2006.7 1260.0 933.3 lbs (3-25) 1740.0 1740.0 2078.3 1305.0 966.7 lbs Max 22.7 ≤ 0.05 fm, OK (3-23), 3.3.5.4 19.0 19.0 22.7 14.3 10.6 psi 8.0 17.9 8.0 17.9 plf 0.155 sq.in ### = 0.18 0.18 0.19 0.18 0.17 sq.in a = (3-28) = 0.77 0.77 0.79 0.74 0.71 inch c = a/0.8 3.3.2(g) = 0.96 0.96 0.99 0.92 0.89 inch (3-27) = 37,830 37,830 38,856 36,500 35,456 lb-in = 44.85 44.85 45.57 43.88 43.09
84.0 psi, per T-3.1.7.2.1 = 84 84 84 84 84psi
= 444 444 444 444 444
3.3.5.4 = 9,780 9,780 9,780 9,780 9,780 lb-in
= 0.39 0.39 0.39 0.39 0.39 in
(3-24) = 235 27,479 116,993 21,413 48,697 lb-in
= 0.01 N/A N/A N/A N/A inch
= N/A 7.22 40.32 5.02 16.19 inch
Strength check 34,047 34,047 34,970 32,850 31,911 lb-in
(3-26) OK OK NG OK NG
Deflection at service load Load combination = D + L + (W or 0.7E) (16-15)
Seismic Wind
Unfactored lateral load, w = 12.5 5.0 plf
50.0 50.0 lbs ` Δs 1,400.0 1,400.0 lbs ### P = = 1,450.0 1,450.0 lbs ### = 0.18 0.18 ### a = = 0.75 0.75 in ### c = a/0.8 = 0.93 0.93 in ### = 44.20 44.20 ### = 42,540 10,126 lb-in ###
(3-30) = N/A N/A inch ###
(3-31) = 13.32 0.52 inch ###
.007(h) (3-29) = 2.94 2.94 inch ###
Check total reinforcement NG OK
Vertical reinforcement = 0.0017 Horizontal reinforcement = 0.0011 Total = 0.0028
Compressive strength, f'm = QE ± 0.2SDSD
Yield strength of rebars, fy = QE ±
Seismic Load QE =Fp = Wp Design response spectral, SDS =
D + 0.5L + 1.QE D + 1.QE
Weight of the wall, Wp = Em = f'm
Reduction factor,
=fr =
Wt. of the wall @ mid height Pw =
Factored load from trib Floor/Roof , Puf =
Factored weight of wall @ mid Ht, Puw = Factored axial load, Pu = Puw+Puf
Pu/Ag =
Factored distributed lateral load, wu =
As =
Ase = (Pu+As.fy)/fy
(Pu+As.fy)/(0.8.f'm.b)
Nominal strength, Mn = (Asfy + Pu)(d - a/2)
Icr = n.Ase.(d-c)2+bc3/3 in4 Modulus of Rupture fr = Ig = b.t3/12 in4 Mu obtained by iteration of deflection ∆u (10times) Mcr = (fr.Ig)/0.5.t δcr = (5.Mcr.h2)/(48.E m.Ig)
Applied ultimate strength, Mu = wu.h2/8+Puf.
e
/
2+Pu.δuMu < Mcru = (5.Mu.h2)/(48.E m.Ig)
Mcr < Mu < Mn,u =cr+ 5.(Mu-Mcr)h2/(48.Em.Icr)
Mn shall not be less than Mu Mn = Mn > Mu
Unfactored Load from trib floor/roof, Pf = Pw = Pf+Pw Ase = (P+As.fy)/fy in2 Ase.fy/(0.8.f'm.b) Icr = n.Ase.(d-c)2+bc3/3 in4 Ms = w.h2/8+Pf.e/2+(Pf+Pw).s Ms < Mcrs = (5.Ms.h2)/(48.Em.Ig) Mcr < Ms < Mns =cr+5.(Ms-Mcr)h2/(48.E m.Icr) Allowable= Ag Ag Ag
Wood member Design: IBC Dense #1
Design Live Load, L 20Psf DF#1 and Better
Design Dead Load, D 10Psf Deflection Limits L/360 DF#1
Load Duration 1.25 (1 for Normal, 1.25 For Roof, 1.15 For Snow Loading) DF#2
Allow soil bearing= 1000 psf L.B with 2x Ledger
Allowable load of L.B. in lbs 270 530 2x12
Size, Member Data Spacing Span Header Rafter/Floor joist Max Span Spacing(inch) 2x14
(Inch) (ft) (Inch) Size Span(ft)*Overhang Ft - Inch 3/8"dia 5/8"Dia DF#2
### 12 14 13 6 875 40 0 ##### 8 6 6 13 2x6 ## 16 12 12 3 95 41 0 #### 8 5 6 12 b ## 19.2 12 11 7 1.6 42 0 ##### 8 4 6 12 d ## 24 11 10 9 1.2 875 43 0 #### 8 3 6 12 CF # 12 18 18 2 CF 1.200 44 0 ##### 8 2 6 12 Cr ## 16 17 16 6 Cr 1.00 45 0 #### 8 1 6 11 E ## 19.2 16 15 6 Fb
## 24 14 14 5 Rafter/Floor Joist Post Spacing Fv
DF#2, Fb= 875 psi w/o Load Duration Span* Overhang 10 11 12 ft 3x6
CF= 1.3 Cr= 1.15 12.8 1.5 Int footing 240 19 20 21 Sq.In Species
For 2x6DF#2 Fb= 1309 psi Ext footing 240 14 14 15 Sq.In size
Fv= 95 psi 13.8 1.5 Int footing 254 20 21 21 Sq.In ##
E= 1.6 psi Ext footing 254 14 15 15 Sq.In DF#1
For 4x10DF#2 Fb= 875 psi 14.8 1.5 Int footing 269 20 21 22 Sq.In 2x8
CF= 1.2 Cr= 1.00 Ext footing 269 14 15 16 Sq.In b
Fv= 95 psi Patio may be supported on concrete slab, provided that the post d
E= 1.6 psi do not support D+L in excess of 750 lbs. CF
R=Repetitive member Used (not more than 24" o/c) Cr
S=Single member Used MINIMUM ROOF LIVE LOAD PER IBC 1607.11.2 E
Lag Bolts shall be min of 5" long 300.0 SQ.FT
* For header with Rafter or Joist at both side, 1.2-.001At Eq. 16-29
spacing (rafter's span) shall be double or average. = 0.90 6x8
Rise per feet, F = 5 :12 6x10
1.2-.05F Eq. 16-32 = 0.95 size Eq. 16-24 = 20(0.9)(0.95) DF#2 17.10 psf b d CF Cr E Fb Fv
RAFTER / OR FLOOR JOIST (Table 1) HEADER (Table 2)
Fb FOOTING (Table 3) Tributary area At = R1 = R2 = Lr = 20R1R2
Min Design Roof Lr = RAFTER SPAN
PER TABLE 1
LAG BOLT, SIZE &
SPACING PER TABLE 2 HEADER, PER TABLE 2
POST SPACING PER TABLE 3 FOOTING SIZE
PER TABLE 3 HEADER, PER TABLE 2