Short Circuit Calculation
Sector Energy D SE PTI NC Steffen Schmidt
Purpose of Short-Circuit Calculations
Dimensioning of switching devices Dynamic dimensioning of switchgear
Thermal rating of electrical devices (e.g. cables) Protection coordination
Fault diagnostic Input data for
Earthing studies
Interference calculations EMC planning
Short-Circuit Calculation Standards
IEC 60909:
Short-Circuit Current Calculation in Three-Phase A.C. Systems
European Standard EN 60909
German National Standard DIN VDE 0102 further National Standards
Engineering Recommendation G74 (UK)
Procedure to Meet the Requirements of IEC 60909 for the
Calculation of Short-Circuit Currents in Three-Phase AC Power Systems
ANSI IIEEE Std. C37.5 (US)
Short-Circuit Calculations Standard IEC 60909
IEC 60909 : Short-circuit currents in three-phase a.c. systems
Part 0: Calculation of currents
Part 1: Factors for the calculation of short-circuit currents
Part 2: Electrical equipment; data for short-circuit current calculations Part 3: Currents during two separate
simultaneous line-to-earth short circuits and partial short-circuit currents flowing through earth Part 4: Examples for the calculation of
Short-Circuit Calculations Scope of IEC 60909
three-phase a.c. systems
low voltage and high voltage systems up to 500 kV nominal frequency of 50 Hz and 60 Hz
balanced and unbalanced short circuits three phase short circuits
two phase short circuits (with and without earth connection) single phase line-to-earth short circuits in systems with solidly
earthed or impedance earthed neutral
two separate simultaneous single-phase line-to-earth short circuits
in a systems with isolated neutral or a resonance earthed neutral (IEC 60909-3)
maximum short circuit currents minimum short circuit currents
Short-Circuit Calculations Types of Short Circuits
3-phase
2-phase
Variation of short circuit current shapes
fault at voltage peak fault at voltage zero crossing fault located in
the network
fault located near generator
Short-Circuit Calculations
Far-from-generator short circuit
Ik” Initial symmetrical short-circuit current
ip Peak short-circuit current
Ik Steady-state short-circuit current
Short-Circuit Calculations
Definitions according IEC 60909 (I)
initial symmetrical short-circuit current Ik”
r.m.s. value of the a.c. symmetrical component of a prospective
(available) short-circuit current, applicable at the instant of short circuit if the impedance remains at zero-time value
initial symmetrical short-circuit power Sk”
fictitious value determined as a product of the initial symmetrical short-circuit current Ik”, the nominal system voltage Un and the factor √3:
NOTE: Sk” is often used to calculate the internal impedance of a network feeder at the
connection point. In this case the definition given should be used in the following form:
" k n " k
3
U
I
S
=
⋅
⋅
2U
c
⋅
=
Short-Circuit Calculations
Definitions according IEC 60909 (II)
decaying (aperiodic) component id.c. of short-circuit current
mean value between the top and bottom envelope of a short-circuit current decaying from an initial value to zero
peak short-circuit current ip
maximum possible instantaneous value of the prospective (available) short-circuit current
NOTE: The magnitude of the peak short-circuit current varies in accordance with the moment at which the short circuit occurs.
Short-Circuit Calculations
Near-to-generator short circuit
Ik” Initial symmetrical short-circuit current
ip Peak short-circuit current
Ik Steady-state short-circuit current
A Initial value of the d.c component
IB Symmetrical short-circuit breaking current
tB
B
I 2 2⋅ ⋅
Short-Circuit Calculations
Definitions according IEC 60909 (III) steady-state short-circuit current Ik
r.m.s. value of the short-circuit current which remains after the decay of the transient phenomena
symmetrical short-circuit breaking current Ib
r.m.s. value of an integral cycle of the symmetrical a.c. component of the prospective short-circuit current at the instant of contact separation of the first pole to open of a switching device
Short-Circuit Calculations
Purpose of Short-Circuit Values
Minimum symmetrical short-circuit current Ik
Selective detection of partial short-circuit currents
Protection setting
Maximum initial symmetrical short-circuit current Ik”
Potential rise; Magnetic fields Earthing, Interference, EMC
Initial symmetrical short-circuit current Ik”
Fault duration Temperature rise of electrical
devices (e.g. cables) Thermal stress to equipment
Peak short-circuit current ip
Forces to electrical devices (e.g. bus bars, cables…) Mechanical stress to
equipment
Symmetrical short-circuit
breaking current Ib
Thermal stress to arcing chamber; arc extinction Breaking capacity of circuit
breakers
Relevant short-circuit current Physical Effect
Standard IEC 60909
Simplifications and Assumption
Assumptions
quasi-static state instead of dynamic calculation
no change in the type of short circuit during fault duration no change in the network during fault duration
arc resistances are not taken into account
impedance of transformers is referred to tap changer in main position neglecting of all shunt impedances except for C0
Short-circuit
Equivalent voltage source at the short-circuit location
A Q Q ZT A ZL ZN F ~ I"K 3 .Un c real network equivalent circuit
Operational data and the passive load of consumers are neglected Tap-changer position of transformers is dispensable
Excitation of generators is dispensable Load flow (local and time) is dispensable
Short circuit in meshed grid
Equivalent voltage source at the short-circuit location
Voltage Factor c
c is a safety factor to consider the following effects:
voltage variations depending on time and place, changing of transformer taps,
neglecting loads and capacitances by calculations, the subtransient behaviour of generators and motors.
1.00 1.10 Medium voltage >1 kV – 35 kV 0.95 0.95 1.05 1.10 Low voltage 100 V – 1000 V
-systems with a tolerance of 6% -systems with a tolerance of 10%
1.00 1.10
High voltage >35 kV
minimum short circuit currents maximum short circuit currents
Nominal voltage
Maximum and minimum Short-Circuit Currents shall be neglected shall be considered Motors Maximum impedance Minimum impedance Network feeders minimum short circuit currents maximum
short circuit currents
Minimum contribution Maximum contribution Power plants Cmin Cmax Voltage factor at maximum temperature at 20°C
Short Circuit Impedances
For network feeders, transformer, overhead lines, cable etc.
impedance of positive sequence system = impedance of negative
sequence system
impedance of zero sequence system usually different topology can be different for zero sequence system
Correction factors for
generators,
generator blocks, network transformer
Network feeders
At a feeder connection point usually one of the following values is given:
the initial symmetrical short circuit current Ik” the initial short-circuit power Sk”
If R/X of the network feeder is unknown, one of the following values can be used:
R/X = 0.1
R/X = 0.0 for high voltage systems >35 kV fed by overhead lines
" k 2 n " k n Q S U c I 3 U c Z = ⋅ ⋅ ⋅ = 2 Q Q ) X / R ( 1 Z X + =
Network transformer Correction of Impedance
ZTK = ZT KT
general
at known conditions of operation
T max T x 6 , 0 1 c 95 , 0 K ⋅ + ⋅ = b T rT b T T max b n T sin ) I I ( x 1 c U U K ϕ + ⋅ =
Network transformer
Impact of Correction Factor
The Correction factor is KT<1.0 for transformers with xT >7.5 %. Reduction of transformer impedance
Increase of short-circuit currents 0.80 0.85 0.90 0.95 1.00 1.05 0 5 10 15 20 xT [%] K T cmax = 1.10 cmax = 1.05
Generator with direct Connection to Network Correction of Impedance
ZGK = ZG KG
general
for continuous operation above rated voltage: UrG (1+pG) instead of UrG rG d max rG n G sin x 1 c U U K ϕ ⋅ ′′ + ⋅ =
Generator Block (Power Station) Correction of Impedance
ZS(O) = (tr2 Z
G +ZTHV) KS(O)
power station with on-load tap changer:
power station without on-load tap changers:
rG T d max 2 rTHV 2 rTLV 2 rG 2 nQ S sin x x 1 c U U U U K ϕ ⋅ − ′′ + ⋅ ⋅ = G Q
(
)
rG d max t rTHV rTLV G rG nQ SO sin x 1 c p 1 U U ) p 1 ( U U K ϕ ⋅ ′′ + ⋅ ± ⋅ ⋅ + =Asynchronous Motors
Motors contribute to the short circuit currents and have to be considered for calculation of maximum short circuit currents
If R/X is unknown, the following values can be used:
R/X = 0.1 medium voltage motors power per pole pair > 1 MW R/X = 0.15 medium voltage motors power per pole pair ≤ 1 MW
rM 2 rM rM LR M S U I / I 1 Z = ⋅ 2 M M M M ) X / R ( 1 Z X + =
Special Regulations for low Voltage Motors
low voltage motors can be neglected if ∑IrM ≤ Ik”
groups of motors can be combined to a equivalent motor ILR/IrM = 5 can be used
Calculation of initial short circuit current Procedure
Set up equivalent circuit in symmetrical components Consider fault conditions
in 3-phase system
transformation into symmetrical components Calculation of fault currents
in symmetrical components
Calculation of initial short circuit current
Equivalent circuit in symmetrical components
positive sequence system
negative sequence system
zero sequence system
(1) (1) (1) (1) (1) (1) (1) (1) (2) (2) (2) (2) (2) (2) (2) (2) (0) (0) (0) (0) (0) (0) (0) (0)
Calculation of initial short circuit current 3-phase short circuit
L1 L2 L3 ~ -Uf 012-system UL1 = – Uf UL2 = a2 (– U f) UL3 = a (– Uf) U(1) = – Uf U(2) = 0 U = 0 (1) r sc3 3 Z U c I ⋅ ⋅ = ′′ L1-L2-L3-system ~ ~ Z(1)l Z(1)r ~ ~ Z(2)l Z(2)r ~ ~ Z(0)l Z(0)r (1) (2) (0) network left of fault location network right of fault location fault location ~ c Un √3 ~ ~
Calculation of 2-phase initial short circuit current L1-L2-L3-system 012-system IL1 = 0 IL2 = – IL3 I(0) = 0 3 n ) 2 ( ) 1 ( U c U U − = − ~ ~ Z(1)l Z(1)r ~ ~ Z(2)l Z(2)r ~ ~ Z(0)l Z(0)r (1) (2) (0) network left of fault location network right of fault location fault location ~ c Un √3 ( )1 ( )2 r sc2 Z Z U c I + ⋅ = ′′ ( ) 2 3 2 sc3 sc2 1 r sc2 ′′ = ′′ ⇒ ⋅ = ′′ I I Z U c I L1 L2 L3 ~ -Uf
Calculation of 2-phase initial short circuit current with ground connection
L1-L2-L3-system 012-system 0 L1 = I 3 n 2 L2 U c a U = − 3 n L3 U c a U = − I = I = I ) 0 ( ) 1 ( n ) 2 ( ) 1 ( 3 U U U c U U − = − = − ~ ~ Z(1)l Z(1)r ~ ~ Z(2)l Z(2)r ~ ~ Z(0)l Z(0)r (1) (2) (0) network left of fault location network right of fault location fault location c Un √3 ~ ( )1 ( )0 r scE2E 2 3 Z Z U c I + ⋅ ⋅ = ′′ L1 L2 L3 ~ -Uf
Calculation of 1-phase initial short circuit current L1 L2 L3 L1-L2-L3-System 012-System I = 0 3 n L1 U c U = − 3 n ) 2 ( ) 1 ( ) 0 ( U c U U U + + = − ~ ~ Z(1)l Z(1)r ~ ~ Z(2)l Z(2)r ~ ~ Z(0)l Z(0)r (1) (2) (0) network left of fault location network right of fault location fault location ~ c Un √3 ~ -Uf (1) (2) (0) r " sc1 3 Z Z Z U c I + + ⋅ ⋅ =
Largest initial short circuit current
Because of Z1 ≅ Z2 the
largest short circuit current can be observed
for Z1 / Z0 < 1
3-phase short circuit
for Z1 / Z0 > 1
2-phase short circuit with
earth connection
Feeding of short circuits
single fed short circuit
multiple fed short circuit
∑
∑
≅ = " sc_part " sc_part " sc I I I SkQ UnQ " ür:1 k3 " sc I G 3~ M 3~ I“scG I“scN I“scMCalculation of short circuit currents by programs (1/3)
Basic equation
i = Y u Y: matrix of admittances (for short circuit)
⋅ − = n r 2 1 nn n1 in i1 2n 21 1n 11 '' sci . . . 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0 . . . . . . 0 0 U U c U U Y Y Y Y Y Y Y Y I
Calculation of short circuit currents by programs (2/3)
Inversion of matrix of admittances
u = Y-1 i = ⋅ − 0 . . . . . . 0 0 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 . . . '' sci nn n1 in ii i1 2n 21 1n 11 r 2 1 I Z Z Z Z Z Z Z Z Z U U c U U
Calculation of short circuit currents by programs (3/3)
from line i:
⇒
from the remaining lines:
calculation of all node voltages
from there -> calculation of all short circuit currents
3 " sci ii r Z I U c ⋅ = − 3 ii r " sci Z U c I ⋅ − = " sci sci sc Z I U = ⋅
Short Circuit Calculation Results Faults at all Buses
Short Circuit Calculation Results Contribution for one Fault Location
Data of sample calculation Network feeder: 110 kV 3 GVA R/X = 0.1 Transformer: 110 / 20 kV 40 MVA uk = 15 % PkrT = 100 kVA Overhead line: 20 kV 10 km R1’ = 0.3 Ω / km X1’ = 0.4 Ω / km
Impedance of Network feeder " k 2 n I S U c Z = ⋅
(
)
GVA 3 kV 20 1 . 1 Z 2 I ⋅ = Ω = 0.1467 ZI RI = 0.0146 Ω XI = 0.1460 ΩImpedance of Transformer n 2 n k T S U u Z = ⋅ Ω =1.5000 ZT RT = 0.0250 Ω XT =1.4998 Ω
(
)
MVA 40 kV 20 15 . 0 Z 2 T = ⋅ 2 n 2 n krT T S U P R = ⋅(
)
(
)
2 2 T MVA 40 kV 20 kVA 100 R = ⋅Impedance of Transformer Correction Factor T max T x 6 . 0 1 c 95 . 0 K ⋅ + ⋅ = 14998 . 0 6 . 0 1 1 . 1 95 . 0 KT ⋅ + ⋅ = 95873 . 0 KT = Ω =1.4381 ZTK RTK = 0.0240 Ω XTK =1.4379 Ω
Impedance of Overhead Line ⋅ =R' RL Ω = 3.0000 RL XI = 4.0000 Ω km 10 km / 3 . 0 RL = Ω ⋅ ⋅ = X' XL km 10 km / 4 . 0 XL = Ω ⋅
Initial Short-Circuit Current – Fault location 1 TK I R R R = + X = XI + XTK Ω + Ω = 0.0146 0.0240 R X = 0.1460Ω+1.4379Ω Ω = 0.0386 R X =1.5839Ω
(
1 1)
n " k X j R 3 U c I ⋅ + ⋅ ⋅ =(
) (
2)
2 " k 5839 . 1 0386 . 0 3 kV 20 1 . 1 I Ω + Ω ⋅ ⋅ = " =Initial Short-Circuit Current – Fault location 2 L TK I R R R R = + + X = XI + XTK + XL Ω + Ω + Ω = 0.0146 0.0240 3.0000 R X = 0.1460Ω+1.4379Ω+ 4.0000Ω Ω = 3.0386 R X = 5.5839Ω
(
1 1)
n " k X j R 3 U c I ⋅ + ⋅ ⋅ =(
) (
2)
2 " k 5839 . 5 0386 . 3 3 kV 20 1 . 1 I Ω + Ω ⋅ ⋅ = kA 0 . 2 I" k =Peak Short-Circuit Current Calculation acc. IEC 60909
maximum possible instantaneous value of expected short circuit current equation for calculation:
i
p=
κ
⋅
2
⋅
I
"kX / R 3 e 98 . 0 02 . 1 + ⋅ − = κ
Peak Short-Circuit Current
Calculation in non-meshed Networks
The peak short-circuit current ip at a short-circuit location, fed from
sources which are not meshed with one another is the sum of the partial short-circuit currents:
M G
M
Peak Short-Circuit Current
Calculation in meshed Networks
Method A: uniform ratio R/X
smallest value of all network branches quite inexact
Method B: ratio R/X at the fault location
factor κb from relation R/X at the fault location (equation or diagram) κ =1,15 κb
Method C: procedure with substitute frequency
factor κ from relation Rc/Xc with substitute frequency fc = 20 Hz
best results for meshed networks f f X R X R c c c ⋅ =
Peak Short-Circuit Current
Fictitious Resistance of Generator
RGf = 0,05 Xd" for generators with UrG > 1 kV and SrG ≥ 100 MVA RGf = 0,07 Xd" for generators with UrG > 1 kV and SrG < 100 MVA RGf = 0,15 Xd" for generators with UrG ≤ 1000 V
Peak Short-Circuit Current – Fault location 1 Ω = 0.0386 R X =1.5839Ω kA 0 . 8 I" k = 0244 . 0 X / R = " k p 2 I i = κ⋅ ⋅ X / R 3 e 98 . 0 02 . 1 + ⋅ − = κ 93 . 1 = κ kA 8 . 21 ip =
Peak Short-Circuit Current – Fault location 2 Ω = 3.0386 R X = 5.5839Ω kA 0 . 2 I" k = 5442 . 0 X / R = " k p 2 I i = κ⋅ ⋅ X / R 3 e 98 . 0 02 . 1 + ⋅ − = κ 21 . 1 = κ kA 4 . 3 i =
Breaking Current Differentiation
Differentiation between short circuits ”near“ or “far“ from generator
Definition short circuit ”near“ to generator
for at least one synchronous machine is: Ik” > 2 ∙ Ir,Generator
or
Ik”with motor > 1.05 ∙ Ik”without motor
Breaking current Ib for short circuit “far“ from generator Ib = Ik”
Breaking Current
Calculation in non-meshed Networks
The breaking current IB at a short-circuit location, fed from sources which are not meshed is the sum of the partial short-circuit currents:
M G
M
IB1 = μ∙I“k
IB = IB1 + IB2 + IB3 + IB4
Breaking current
Decay of Current fed from Generators
IB = μ ∙ I“k
Factor μ to consider the decay of short circuit current fed from generators.
Breaking current
Decay of Current fed from Asynchronous Motors
IB = μ ∙ q ∙ I“k
Factor q to consider the decay of short circuit current fed from asynchronous motors.
Breaking Current
Calculation in meshed Networks
Simplified calculation: Ib = Ik”
For increased accuracy can be used:
X“diK subtransient reactance of the synchronous machine (i)
X“Mj reactance of the asynchronous motors (j)
I“ , I“ " kMj j j j n Mj " kGi i i n Gi " k b (1 q ) I 3 / U c " U I ) 1 ( 3 / U c " U I I ⋅ −µ ⋅ ⋅ ∆ − ⋅ µ − ⋅ ⋅ ∆ − =
∑
∑
" kGi " diK " Gi jX I U = ⋅ ∆ Mj" "kMj " Mj jX I U = ⋅ ∆Continuous short circuit current
Continuous short circuit current Ik
r.m.s. value of short circuit current after decay of all transient
effects
depending on type and excitation of generators
statement in standard only for single fed short circuit calculation by factors (similar to breaking current)
Continuous short circuit current is normally not calculated by network calculation programs.
For short circuits far from generator and as worst case estimation Ik = I”k
Short-circuit with preload Principle
A Load flow calculation that considers all network parameters, such as loads, tap positions, etc.
B Place voltage source with the voltage that was determined by the load flow calculation at the fault location.
Short-circuit with preload Example
A Load flow calculation
Short-circuit with preload Results 720V 336V 592.11V 1000V 192.0A 168A 197.37A 203.95A
Short-circuit with preload
~ ~ 365.37A 720V -0V 720V 700V -364V 336V 900. V -307.89V 592.11V 1000V -0V 1000V 10A 182A 192A 40A 208A 168A 40. A 157.37A 197.37A 50. A 153.95A 203.95A
Superposition: Load flow + feed back
~ ~ 365.37A 24A 6.58A 720V 1000V 40A 40A 50A Load flow ~ ~ 50A 10A Ω 2 3Ω 2Ω 10A 2Ω Ω 14 780V 900V Ω 90 700V 0V 0V 208.0A 365.3A 153.95A
Short-circuit: feed back 26A 3.42A 182A 780V 307.89V 364V 157.37A
Contact
Steffen Schmidt
Senior Consultant
Siemens AG, Energy Sector E D SE PTI NC Freyeslebenstr. 1 91058 Erlangen Phone: +49 9131 - 7 32764 Fax: +49 9131 - 7 32525 E-mail: [email protected]