• No results found

8698462 Short Circuit Calculations

N/A
N/A
Protected

Academic year: 2021

Share "8698462 Short Circuit Calculations"

Copied!
72
0
0

Loading.... (view fulltext now)

Full text

(1)

Short Circuit Calculation

Sector Energy D SE PTI NC Steffen Schmidt

(2)
(3)

Purpose of Short-Circuit Calculations

Dimensioning of switching devicesDynamic dimensioning of switchgear

Thermal rating of electrical devices (e.g. cables)Protection coordination

Fault diagnosticInput data for

Earthing studies

Interference calculationsEMC planning

(4)

Short-Circuit Calculation Standards

IEC 60909:

Short-Circuit Current Calculation in Three-Phase A.C. Systems

European Standard EN 60909

German National Standard DIN VDE 0102further National Standards

Engineering Recommendation G74 (UK)

Procedure to Meet the Requirements of IEC 60909 for the

Calculation of Short-Circuit Currents in Three-Phase AC Power Systems

ANSI IIEEE Std. C37.5 (US)

(5)

Short-Circuit Calculations Standard IEC 60909

IEC 60909 : Short-circuit currents in three-phase a.c. systems

Part 0: Calculation of currents

Part 1: Factors for the calculation of short-circuit currents

Part 2: Electrical equipment; data for short-circuit current calculations Part 3: Currents during two separate

simultaneous line-to-earth short circuits and partial short-circuit currents flowing through earth Part 4: Examples for the calculation of

(6)

Short-Circuit Calculations Scope of IEC 60909

three-phase a.c. systems

low voltage and high voltage systems up to 500 kV  nominal frequency of 50 Hz and 60 Hz

balanced and unbalanced short circuitsthree phase short circuits

two phase short circuits (with and without earth connection)  single phase line-to-earth short circuits in systems with solidly

earthed or impedance earthed neutral

two separate simultaneous single-phase line-to-earth short circuits

in a systems with isolated neutral or a resonance earthed neutral (IEC 60909-3)

maximum short circuit currentsminimum short circuit currents

(7)

Short-Circuit Calculations Types of Short Circuits

3-phase

2-phase

(8)

Variation of short circuit current shapes

fault at voltage peak fault at voltage zero crossing fault located in

the network

fault located near generator

(9)

Short-Circuit Calculations

Far-from-generator short circuit

Ik” Initial symmetrical short-circuit current

ip Peak short-circuit current

Ik Steady-state short-circuit current

(10)

Short-Circuit Calculations

Definitions according IEC 60909 (I)

initial symmetrical short-circuit current Ik

r.m.s. value of the a.c. symmetrical component of a prospective

(available) short-circuit current, applicable at the instant of short circuit if the impedance remains at zero-time value

initial symmetrical short-circuit power Sk

fictitious value determined as a product of the initial symmetrical short-circuit current Ik”, the nominal system voltage Un and the factor √3:

NOTE: Sk” is often used to calculate the internal impedance of a network feeder at the

connection point. In this case the definition given should be used in the following form:

" k n " k

3

U

I

S

=

2

U

c

=

(11)

Short-Circuit Calculations

Definitions according IEC 60909 (II)

decaying (aperiodic) component id.c. of short-circuit current

mean value between the top and bottom envelope of a short-circuit current decaying from an initial value to zero

peak short-circuit current ip

maximum possible instantaneous value of the prospective (available) short-circuit current

NOTE: The magnitude of the peak short-circuit current varies in accordance with the moment at which the short circuit occurs.

(12)

Short-Circuit Calculations

Near-to-generator short circuit

Ik” Initial symmetrical short-circuit current

ip Peak short-circuit current

Ik Steady-state short-circuit current

A Initial value of the d.c component

IB Symmetrical short-circuit breaking current

tB

B

I 2 2⋅ ⋅

(13)

Short-Circuit Calculations

Definitions according IEC 60909 (III) steady-state short-circuit current Ik

r.m.s. value of the short-circuit current which remains after the decay of the transient phenomena

symmetrical short-circuit breaking current Ib

r.m.s. value of an integral cycle of the symmetrical a.c. component of the prospective short-circuit current at the instant of contact separation of the first pole to open of a switching device

(14)

Short-Circuit Calculations

Purpose of Short-Circuit Values

Minimum symmetrical short-circuit current Ik

Selective detection of partial short-circuit currents

Protection setting

Maximum initial symmetrical short-circuit current Ik

Potential rise; Magnetic fields Earthing, Interference, EMC

Initial symmetrical short-circuit current Ik

Fault duration Temperature rise of electrical

devices (e.g. cables) Thermal stress to equipment

Peak short-circuit current ip

Forces to electrical devices (e.g. bus bars, cables…) Mechanical stress to

equipment

Symmetrical short-circuit

breaking current Ib

Thermal stress to arcing chamber; arc extinction Breaking capacity of circuit

breakers

Relevant short-circuit current Physical Effect

(15)

Standard IEC 60909

Simplifications and Assumption

Assumptions

quasi-static state instead of dynamic calculation

no change in the type of short circuit during fault durationno change in the network during fault duration

arc resistances are not taken into account

impedance of transformers is referred to tap changer in main position  neglecting of all shunt impedances except for C0

(16)
(17)

Short-circuit

Equivalent voltage source at the short-circuit location

A Q Q ZT A ZL ZN F ~ I"K 3 .Un c real network equivalent circuit

Operational data and the passive load of consumers are neglected Tap-changer position of transformers is dispensable

Excitation of generators is dispensable Load flow (local and time) is dispensable

(18)

Short circuit in meshed grid

Equivalent voltage source at the short-circuit location

(19)

Voltage Factor c

c is a safety factor to consider the following effects:

voltage variations depending on time and place,changing of transformer taps,

neglecting loads and capacitances by calculations,the subtransient behaviour of generators and motors.

1.00 1.10 Medium voltage >1 kV – 35 kV 0.95 0.95 1.05 1.10 Low voltage 100 V – 1000 V

-systems with a tolerance of 6% -systems with a tolerance of 10%

1.00 1.10

High voltage >35 kV

minimum short circuit currents maximum short circuit currents

Nominal voltage

(20)

Maximum and minimum Short-Circuit Currents shall be neglected shall be considered Motors Maximum impedance Minimum impedance Network feeders minimum short circuit currents maximum

short circuit currents

Minimum contribution Maximum contribution Power plants Cmin Cmax Voltage factor at maximum temperature at 20°C

(21)
(22)

Short Circuit Impedances

For network feeders, transformer, overhead lines, cable etc.

impedance of positive sequence system = impedance of negative

sequence system

impedance of zero sequence system usually differenttopology can be different for zero sequence system

Correction factors for

generators,

generator blocks, network transformer

(23)

Network feeders

At a feeder connection point usually one of the following values is given:

 the initial symmetrical short circuit current Ik”  the initial short-circuit power Sk

If R/X of the network feeder is unknown, one of the following values can be used:

R/X = 0.1

R/X = 0.0 for high voltage systems >35 kV fed by overhead lines

" k 2 n " k n Q S U c I 3 U c Z = ⋅ ⋅ ⋅ = 2 Q Q ) X / R ( 1 Z X + =

(24)

Network transformer Correction of Impedance

ZTK = ZT KT

general

 at known conditions of operation

T max T x 6 , 0 1 c 95 , 0 K ⋅ + ⋅ = b T rT b T T max b n T sin ) I I ( x 1 c U U K ϕ + ⋅ =

(25)

Network transformer

Impact of Correction Factor

The Correction factor is KT<1.0 for transformers with xT >7.5 %. Reduction of transformer impedance

Increase of short-circuit currents 0.80 0.85 0.90 0.95 1.00 1.05 0 5 10 15 20 xT [%] K T cmax = 1.10 cmax = 1.05

(26)

Generator with direct Connection to Network Correction of Impedance

ZGK = ZG KG

general

 for continuous operation above rated voltage: UrG (1+pG) instead of UrG rG d max rG n G sin x 1 c U U K ϕ ⋅ ′′ + ⋅ =

(27)

Generator Block (Power Station) Correction of Impedance

ZS(O) = (tr2 Z

G +ZTHV) KS(O)

power station with on-load tap changer:

 power station without on-load tap changers:

rG T d max 2 rTHV 2 rTLV 2 rG 2 nQ S sin x x 1 c U U U U K ϕ ⋅ − ′′ + ⋅ ⋅ = G Q

(

)

rG d max t rTHV rTLV G rG nQ SO sin x 1 c p 1 U U ) p 1 ( U U K ϕ ⋅ ′′ + ⋅ ± ⋅ ⋅ + =

(28)

Asynchronous Motors

Motors contribute to the short circuit currents and have to be considered for calculation of maximum short circuit currents

If R/X is unknown, the following values can be used:

R/X = 0.1 medium voltage motors power per pole pair > 1 MWR/X = 0.15 medium voltage motors power per pole pair ≤ 1 MW

rM 2 rM rM LR M S U I / I 1 Z = ⋅ 2 M M M M ) X / R ( 1 Z X + =

(29)

Special Regulations for low Voltage Motors

 low voltage motors can be neglected if ∑IrM ≤ Ik

groups of motors can be combined to a equivalent motor  ILR/IrM = 5 can be used

(30)
(31)

Calculation of initial short circuit current Procedure

Set up equivalent circuit in symmetrical components Consider fault conditions

in 3-phase system

transformation into symmetrical componentsCalculation of fault currents

in symmetrical components

(32)

Calculation of initial short circuit current

Equivalent circuit in symmetrical components

positive sequence system

negative sequence system

zero sequence system

(1) (1) (1) (1) (1) (1) (1) (1) (2) (2) (2) (2) (2) (2) (2) (2) (0) (0) (0) (0) (0) (0) (0) (0)

(33)

Calculation of initial short circuit current 3-phase short circuit

L1 L2 L3 ~ -Uf 012-system UL1 = – Uf UL2 = a2 (– U f) UL3 = a (– Uf) U(1) = – Uf U(2) = 0 U = 0 (1) r sc3 3 Z U c I ⋅ ⋅ = ′′ L1-L2-L3-system ~ ~ Z(1)l Z(1)r ~ ~ Z(2)l Z(2)r ~ ~ Z(0)l Z(0)r (1) (2) (0) network left of fault location network right of fault location fault location ~ c Un √3 ~ ~

(34)

Calculation of 2-phase initial short circuit current L1-L2-L3-system 012-system IL1 = 0 IL2 = – IL3 I(0) = 0 3 n ) 2 ( ) 1 ( U c U U − = − ~ ~ Z(1)l Z(1)r ~ ~ Z(2)l Z(2)r ~ ~ Z(0)l Z(0)r (1) (2) (0) network left of fault location network right of fault location fault location ~ c Un √3 ( )1 ( )2 r sc2 Z Z U c I + ⋅ = ′′ ( ) 2 3 2 sc3 sc2 1 r sc2 ′′ = ′′ ⇒ ⋅ = ′′ I I Z U c I L1 L2 L3 ~ -Uf

(35)

Calculation of 2-phase initial short circuit current with ground connection

L1-L2-L3-system 012-system 0 L1 = I 3 n 2 L2 U c a U = − 3 n L3 U c a U = − I = I = I ) 0 ( ) 1 ( n ) 2 ( ) 1 ( 3 U U U c U U − = − = − ~ ~ Z(1)l Z(1)r ~ ~ Z(2)l Z(2)r ~ ~ Z(0)l Z(0)r (1) (2) (0) network left of fault location network right of fault location fault location c Un √3 ~ ( )1 ( )0 r scE2E 2 3 Z Z U c I + ⋅ ⋅ = ′′ L1 L2 L3 ~ -Uf

(36)

Calculation of 1-phase initial short circuit current L1 L2 L3 L1-L2-L3-System 012-System I = 0 3 n L1 U c U = − 3 n ) 2 ( ) 1 ( ) 0 ( U c U U U + + = − ~ ~ Z(1)l Z(1)r ~ ~ Z(2)l Z(2)r ~ ~ Z(0)l Z(0)r (1) (2) (0) network left of fault location network right of fault location fault location ~ c Un √3 ~ -Uf (1) (2) (0) r " sc1 3 Z Z Z U c I + + ⋅ ⋅ =

(37)

Largest initial short circuit current

Because of Z1 Z2 the

largest short circuit current can be observed

for Z1 / Z0 < 1

3-phase short circuit

for Z1 / Z0 > 1

2-phase short circuit with

earth connection

(38)

Feeding of short circuits

single fed short circuit

multiple fed short circuit

≅ = " sc_part " sc_part " sc I I I SkQ UnQ " ür:1 k3 " sc I G 3~ M 3~ I“scG I“scN I“scM

(39)

Calculation of short circuit currents by programs (1/3)

Basic equation

i = Y u Y: matrix of admittances (for short circuit)

                                ⋅ −                                 =                                 n r 2 1 nn n1 in i1 2n 21 1n 11 '' sci . . . 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0 . . . . . . 0 0 U U c U U Y Y Y Y Y Y Y Y I

(40)

Calculation of short circuit currents by programs (2/3)

Inversion of matrix of admittances

u = Y-1 i                                                                 =                                 ⋅ − 0 . . . . . . 0 0 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 . . . '' sci nn n1 in ii i1 2n 21 1n 11 r 2 1 I Z Z Z Z Z Z Z Z Z U U c U U

(41)

Calculation of short circuit currents by programs (3/3)

from line i:

from the remaining lines:

calculation of all node voltages

from there -> calculation of all short circuit currents

3 " sci ii r Z I U c ⋅ = − 3 ii r " sci Z U c I ⋅ − = " sci sci sc Z I U = ⋅

(42)

Short Circuit Calculation Results Faults at all Buses

(43)

Short Circuit Calculation Results Contribution for one Fault Location

(44)
(45)

Data of sample calculation Network feeder: 110 kV 3 GVA R/X = 0.1 Transformer: 110 / 20 kV 40 MVA uk = 15 % PkrT = 100 kVA Overhead line: 20 kV 10 km R1’ = 0.3 Ω / km X1’ = 0.4 Ω / km

(46)

Impedance of Network feeder " k 2 n I S U c Z = ⋅

(

)

GVA 3 kV 20 1 . 1 Z 2 I ⋅ = Ω = 0.1467 ZI RI = 0.0146 Ω XI = 0.1460 Ω

(47)

Impedance of Transformer n 2 n k T S U u Z = ⋅ Ω =1.5000 ZT RT = 0.0250 Ω XT =1.4998 Ω

(

)

MVA 40 kV 20 15 . 0 Z 2 T = ⋅ 2 n 2 n krT T S U P R = ⋅

(

)

(

)

2 2 T MVA 40 kV 20 kVA 100 R = ⋅

(48)

Impedance of Transformer Correction Factor T max T x 6 . 0 1 c 95 . 0 K ⋅ + ⋅ = 14998 . 0 6 . 0 1 1 . 1 95 . 0 KT ⋅ + ⋅ = 95873 . 0 KT = Ω =1.4381 ZTK RTK = 0.0240 Ω XTK =1.4379 Ω

(49)

Impedance of Overhead Line  ⋅ =R' RL Ω = 3.0000 RL XI = 4.0000 Ω km 10 km / 3 . 0 RL = Ω ⋅  ⋅ = X' XL km 10 km / 4 . 0 XL = Ω ⋅

(50)

Initial Short-Circuit Current – Fault location 1 TK I R R R = + X = XI + XTK Ω + Ω = 0.0146 0.0240 R X = 0.1460Ω+1.4379Ω Ω = 0.0386 R X =1.5839

(

1 1

)

n " k X j R 3 U c I ⋅ + ⋅ ⋅ =

(

) (

2

)

2 " k 5839 . 1 0386 . 0 3 kV 20 1 . 1 I Ω + Ω ⋅ ⋅ = " =

(51)

Initial Short-Circuit Current – Fault location 2 L TK I R R R R = + + X = XI + XTK + XL Ω + Ω + Ω = 0.0146 0.0240 3.0000 R X = 0.1460Ω+1.4379Ω+ 4.0000Ω Ω = 3.0386 R X = 5.5839

(

1 1

)

n " k X j R 3 U c I ⋅ + ⋅ ⋅ =

(

) (

2

)

2 " k 5839 . 5 0386 . 3 3 kV 20 1 . 1 I Ω + Ω ⋅ ⋅ = kA 0 . 2 I" k =

(52)
(53)

Peak Short-Circuit Current Calculation acc. IEC 60909

maximum possible instantaneous value of expected short circuit current equation for calculation:

i

p

=

κ

2

I

"k

X / R 3 e 98 . 0 02 . 1 + ⋅ − = κ

(54)

Peak Short-Circuit Current

Calculation in non-meshed Networks

The peak short-circuit current ip at a short-circuit location, fed from

sources which are not meshed with one another is the sum of the partial short-circuit currents:

M G

M

(55)

Peak Short-Circuit Current

Calculation in meshed Networks

Method A: uniform ratio R/X

smallest value of all network branchesquite inexact

Method B: ratio R/X at the fault location

 factor κb from relation R/X at the fault location (equation or diagram)  κ =1,15 κb

Method C: procedure with substitute frequency

 factor κ from relation Rc/Xc with substitute frequency fc = 20 Hz 

best results for meshed networks f f X R X R c c c ⋅ =

(56)

Peak Short-Circuit Current

Fictitious Resistance of Generator

 RGf = 0,05 Xd" for generators with UrG > 1 kV and SrG ≥ 100 MVA  RGf = 0,07 Xd" for generators with UrG > 1 kV and SrG < 100 MVA  RGf = 0,15 Xd" for generators with UrG ≤ 1000 V

(57)

Peak Short-Circuit Current – Fault location 1 Ω = 0.0386 R X =1.5839Ω kA 0 . 8 I" k = 0244 . 0 X / R = " k p 2 I i = κ⋅ ⋅ X / R 3 e 98 . 0 02 . 1 + − = κ 93 . 1 = κ kA 8 . 21 ip =

(58)

Peak Short-Circuit Current – Fault location 2 Ω = 3.0386 R X = 5.5839Ω kA 0 . 2 I" k = 5442 . 0 X / R = " k p 2 I i = κ⋅ ⋅ X / R 3 e 98 . 0 02 . 1 + − = κ 21 . 1 = κ kA 4 . 3 i =

(59)
(60)

Breaking Current Differentiation

Differentiation between short circuits ”near“ or “far“ from generator

Definition short circuit ”near“ to generator

 for at least one synchronous machine is: Ik” > 2 ∙ Ir,Generator

or

 Ikwith motor > 1.05 ∙ Ikwithout motor

Breaking current Ib for short circuit “far“ from generator Ib = Ik

(61)

Breaking Current

Calculation in non-meshed Networks

The breaking current IB at a short-circuit location, fed from sources which are not meshed is the sum of the partial short-circuit currents:

M G

M

IB1 = μ∙I“k

IB = IB1 + IB2 + IB3 + IB4

(62)

Breaking current

Decay of Current fed from Generators

 IB = μ ∙ I“k

Factor μ to consider the decay of short circuit current fed from generators.

(63)

Breaking current

Decay of Current fed from Asynchronous Motors

 IB = μ ∙ q ∙ I“k

Factor q to consider the decay of short circuit current fed from asynchronous motors.

(64)

Breaking Current

Calculation in meshed Networks

Simplified calculation: Ib = Ik

For increased accuracy can be used:

X“diK subtransient reactance of the synchronous machine (i)

X“Mj reactance of the asynchronous motors (j)

I“ , I“ " kMj j j j n Mj " kGi i i n Gi " k b (1 q ) I 3 / U c " U I ) 1 ( 3 / U c " U I I ⋅ −µ ⋅ ⋅ ∆ − ⋅ µ − ⋅ ⋅ ∆ − =

" kGi " diK " Gi jX I U = ⋅ ∆ Mj" "kMj " Mj jX I U = ⋅ ∆

(65)

Continuous short circuit current

Continuous short circuit current Ik

r.m.s. value of short circuit current after decay of all transient

effects

depending on type and excitation of generators

statement in standard only for single fed short circuitcalculation by factors (similar to breaking current)

Continuous short circuit current is normally not calculated by network calculation programs.

For short circuits far from generator and as worst case estimation Ik = I”k

(66)
(67)

Short-circuit with preload Principle

A Load flow calculation that considers all network parameters, such as loads, tap positions, etc.

B Place voltage source with the voltage that was determined by the load flow calculation at the fault location.

(68)

Short-circuit with preload Example

A Load flow calculation

(69)

Short-circuit with preload Results 720V 336V 592.11V 1000V 192.0A 168A 197.37A 203.95A

Short-circuit with preload

~ ~ 365.37A 720V -0V 720V 700V -364V 336V 900. V -307.89V 592.11V 1000V -0V 1000V 10A 182A 192A 40A 208A 168A 40. A 157.37A 197.37A 50. A 153.95A 203.95A

Superposition: Load flow + feed back

~ ~ 365.37A 24A 6.58A 720V 1000V 40A 40A 50A Load flow ~ ~ 50A 10A Ω 2 3Ω 2Ω 10A 2Ω Ω 14 780V 900V Ω 90 700V 0V 0V 208.0A 365.3A 153.95A

Short-circuit: feed back 26A 3.42A 182A 780V 307.89V 364V 157.37A

(70)
(71)

Contact

Steffen Schmidt

Senior Consultant

Siemens AG, Energy Sector E D SE PTI NC Freyeslebenstr. 1 91058 Erlangen Phone: +49 9131 - 7 32764 Fax: +49 9131 - 7 32525 E-mail: [email protected]

(72)

References

Related documents

For operating voltages below 1/K times rated maximum voltage, the required symmetrical interrupting capability of the circuit breaker shall be equal to K times the rated

The three-phase symmetrical short-circuit calculation of the equivalent boundary nodes in the big data of the original northwest power grid in 2016 is obtained, and the short

If the short circuit of the IGBT occurs across the terminals of the drive, the low inductance of the short circuit results in high di/dt of the short circuit current and the

3) Determine the minimum cable size based on voltage drop considerations 4) Determine the minimum cable size based on short circuit temperature rise 5) Determine the minimum

The forces generated by short-circuit forces are very important for high- voltage bundle conductor lines, medium-voltage distribution lines, and substations, where spacer

This paper analyses the effect of the fault location, for either 10 kV increment or -10 kV decrement of V TCVR voltage, on the symmetrical current and voltage components as well

 The MVA method can also be used to calculate the voltage drop during large e voltage drop during large motor starting. The The  voltage drop is equal to the motor starting MVA

circuit. Its initial value. 6  : Simplified network diagram. 7  : Graphical presentation and decomposition of a : Graphical presentation and decomposition of a short-circuit