Active Line Module

Line power factor

• Basic fundamental (cosϕ1) 1 (factory setting),

can be altered by inputting a reactive current setpoint

• Total (λ) 1 (factory setting)

Efficiency >97.5 % (including Active Interface Module)

DC link voltage The DC link voltage is regulated and can be adjusted as a voltage decoupled from the line voltage.

Factory setting of the DC link voltage: 1.5 × line voltage Radio interference suppression

(standard)

Category C3 to EN 61800-3 (with Active Interface Module)

Air-cooled Active Line Modules in chassis format

7

Line voltage 380 ... 480 V 3 AC Active Line Modules

6SL3330-7TE32-1AA3

6SL3330-7TE32-6AA3

6SL3330-7TE33-8AA3

6SL3330-7TE35-0AA3

6SL3330-7TE36-1AA3 Rated power

• At Irated DC (50 Hz 400 V) kW 132 160 235 300 380

• At IH DC (50 Hz 400 V) kW 115 145 210 270 335

• At Irated DC (60 Hz 460 V) hp 200 250 400 500 600

• At IH DC (60 Hz 460 V) hp 150 200 300 400 500

DC link current

• Rated current Irated DC A 235 291 425 549 678

• Base-load current IH DC 1) A 209 259 378 489 603

• Maximum current Imax DC A 352 436 637 823 1017

Infeed/regenerative feedback current

• Rated current Irated I A 210 260 380 490 605

• Maximum current Imax I A 315 390 570 735 907

Current demand

• 24 V DC auxiliary power supply A 1.1 1.1 1.35 1.35 1.4

• 400 V AC A 0.63 1.13 1.8 1.8 3.6

DC link capacitance

• Active Line Module μF 4200 5200 7800 9600 12600

• Drive line-up, max. μF 41600 41600 76800 76800 134400

Power loss, max. 2)

• At 50 Hz 400 V kW 2.2 2.7 3.9 4.8 6.2

• At 60 Hz 460 V kW 2.3 2.9 4.2 5.1 6.6

Cooling air requirement m3/s (ft3/s) 0.17 (6.0) 0.23 (8.1) 0.36 (12.7) 0.36 (12.7) 0.78 (27.5) Sound pressure level LpA3)

(1 m) at 50/60 Hz

dB 64/67 71/71 69/73 69/73 70/73

Line connection U1, V1, W1

Flat connector for M10 screw

Flat connector for M10 screw

Flat connector for M10 screw

Flat connector for M10 screw

Flat connector for M12 screw

• Conductor cross section, max. (IEC) mm2 2 × 185 2 × 185 2 × 240 2 × 240 4 × 240

DC link connection DCP, DCN

M10 screw M10 screw M10 screw M10 screw 4 × hole for M12

• Conductor cross section, max. (IEC) mm2 2 × 185 2 × 185 2 × 240 2 × 240 Busbar

PE1/GND connection M10 screw M10 screw M10 screw M10 screw M12 screw

• Conductor cross section, max. (IEC) mm2 2 × 185 2 × 185 2 × 240 2 × 240 240

PE2/GND connection M10 screw M10 screw M10 screw M10 screw 2 × M12 screw

• Conductor cross section, max. (IEC) mm2 2 × 185 2 × 185 2 × 240 2 × 240 2 × 240

Cable length, max. 4)

• Shielded m (ft) 2700 (8859) 2700 (8859) 2700 (8859) 2700 (8859) 3900 (12796)

• Unshielded m (ft) 4050 (13288) 4050 (13288) 4050 (13288) 4050 (13288) 5850 (19194)

Degree of protection IP20 IP20 IP20 IP20 IP00

Dimensions

• Width mm (in) 326 (12.8) 326 (12.8) 326 (12.8) 326 (12.8) 503 (19.8)

• Height mm (in) 1400 (55.1) 1400 (55.1) 1533 (60.3) 1533 (60.3) 1475 (58.1)

• Depth mm (in) 356 (14.0) 356 (14.0) 545 (21.5) 545 (21.5) 540 (21.3)

Weight, approx. kg (lb) 95 (209) 95 (209) 136 (300) 136 (300) 290 (639)

Frame size FX FX GX GX HX

Minimum short-circuit current5) A 6200 10500 10500 8000 9200

1) The base-load current IH DC is the basis for a duty cycle of 150 % for 60 s 4) Total of all motor cables and DC link. Longer cable lengths for specific

Technical specifications (continued)

Air-cooled Active Line Modules in chassis format

7

Technical specifications (continued)

Line voltage 380 ... 480 V 3 AC Active Line Modules

6SL3330-7TE37-5AA3

6SL3330-7TE38-4AA3

6SL3330-7TE41-0AA3

6SL3330-7TE41-2AA3

6SL3330-7TE41-4AA3 Rated power

• At Irated DC (50 Hz 400 V) kW 450 500 630 800 900

• At IH DC (50 Hz 400 V) kW 400 465 545 690 780

• At Irated DC (60 Hz 460 V) hp 600 700 900 1000 1250

• At IH DC (60 Hz 460 V) hp 600 700 800 900 1000

DC link current

• Rated current Irated DC A 835 940 1103 1412 1574

• Base-load current IH DC1) A 700 837 982 1255 1401

• Maximum current Imax DC A 1252 1410 1654 2120 2361

Infeed/regenerative feedback current

• Rated current Irated I A 745 840 985 1260 1405

• Maximum current Imax I A 1117 1260 1477 1890 2107

Current demand

• 24 V DC auxiliary power supply A 1.4 1.4 1.5 1.7 1.7

• 400 V AC A 3.6 3.6 5.4 5.4 5.4

DC link capacitance

• Active Line Module μF 15600 16800 18900 26100 28800

• Drive line-up, max. μF 134400 134400 230400 230400 230400

Power loss, max. 2)

• At 50 Hz 400 V kW 7.3 7.7 10.1 12.1 13.3

• At 60 Hz 460 V kW 7.7 8.2 10.8 13.0 14.2

Cooling air requirement m3/s (ft3/s) 0.78 (27.5) 0.78 (27.5) 1.08 (38.1) 1.08 (38.1) 1.08 (38.1) Sound pressure level LpA3)

(1 m) at 50/60 Hz

dB 70/73 70/73 71/73 71/73 71/73

Line connection U1, V1, W1

Flat connector for M12 screw

Flat connector for M12 screw

Flat connector for M12 screw

Flat connector for M12 screw

Flat connector for M12 screw

• Conductor cross section, max. (IEC) mm2 4 × 240 4 × 240 6 × 240 6 × 240 6 × 240

DC link connection DCP, DCN

4 × hole for M12 4 × hole for M12 4 × hole for M12 4 × hole for M12 4 × hole for M12

• Conductor cross section, max. (IEC) mm2 Busbar Busbar Busbar Busbar Busbar

PE1/GND connection M12 screw M12 screw M12 screw M12 screw M12 screw

• Conductor cross section, max. (IEC) mm2 240 240 240 240 240

PE2/GND connection 2 × M12 screw 2 × M12 screw 3 × M12 screw 3 × M12 screw 3 × M12 screw

• Conductor cross section, max. (IEC) mm2 2 × 240 2 × 240 3 × 240 3 × 240 3 × 240

Cable length, max. 4)

• Shielded m (ft) 3900 (12796) 3900 (12796) 3900 (12796) 3900 (12796) 3900 (12796)

• Unshielded m (ft) 5850 (19194) 5850 (19194) 5850 (19194) 5850 (19194) 5850 (19194)

Degree of protection IP00 IP00 IP00 IP00 IP00

Dimensions

• Width mm (in) 503 (19.8) 503 (19.8) 704 (27.7) 704 (27.7) 704 (27.7)

• Height mm (in) 1475 (58.1) 1475 (58.1) 1480 (58.3) 1480 (58.3) 1480 (58.3)

• Depth mm (in) 540 (21.3) 540 (21.3) 550 (21.6) 550 (21.6) 550 (21.6)

Weight, approx. kg (lb) 290 (639) 290 (639) 450 (992) 450 (992) 450 (992)

Frame size HX HX JX JX JX

Minimum short-circuit current5) A 8800 10400 16000 21000 21000

1) The base-load current IH DC is the basis for a duty cycle of 150 % for 60 s or Imax DC for 5 s with a duty cycle duration of 300 s.

2) The specified power loss represents the maximum value at 100 % utilization.

The value is lower under normal operating conditions.

4) Total of all motor cables and DC link. Longer cable lengths for specific configurations are available on request. For additional information, please refer to the SINAMICS Low Voltage Engineering Manual.

5) Current required for reliably triggering protective devices.

Air-cooled Active Line Modules in chassis format

7

Technical specifications (continued)

Line voltage 500 ... 690 V 3 AC Active Line Modules

6SL3330-7TG35-8AA3 6SL3330-7TG37-4AA3 6SL3330-7TG41-0AA3 6SL3330-7TG41-3AA3 Rated power

• At Irated DC (50 Hz 690 V) kW 630 800 1100 1400

• At IH DC (50 Hz 690 V) kW 620 705 980 1215

• At Irated DC (50 Hz 500 V) kW 447 560 780 965

• At IH DC (50 Hz 500 V) kW 450 510 710 880

• At Irated DC (60 Hz 575 V) hp 675 900 1250 1500

• At IH DC (60 Hz 575 V) hp 506 600 1000 1250

DC link current

• Rated current Irated DC A 644 823 1148 1422

• Base-load current IH DC 1) A 573 732 1022 1266

• Maximum current Imax DC A 966 1234 1722 2133

Infeed/regenerative feedback current

• Rated current Irated I A 575 735 1025 1270

• Maximum current Imax I A 862 1102 1537 1905

Current demand

• 24 V DC auxiliary power supply A 1.4 1.5 1.7 1.7

• 500 V AC A 3.0 4.4 4.4 4.4

• 690 V AC A 2.1 3.1 3.1 3.1

DC link capacitance

• Active Line Module μF 7400 11100 14400 19200

• Drive line-up, max. μF 59200 153600 153600 153600

Power loss, max. 2)

• At 50 Hz 690 V kW 6.8 10.2 13.6 16.5

• At 60 Hz 575 V kW 6.2 9.6 12.9 15.3

Cooling air requirement m3/s (ft3/s) 0.78 (27.5) 1.08 (38.1) 1.08 (38.1) 1.08 (38.1) Sound pressure level LpA3)

(1 m) at 50/60 Hz

dB 70/73 71/73 71/73 71/73

Line connection U1, V1, W1

Flat connector for M12 screw

Flat connector for M12 screw

Flat connector for M12 screw

Flat connector for M12 screw

• Conductor cross section, max. (IEC) mm2 4 × 240 6 × 240 6 × 240 6 × 240

DC link connection DCP, DCN

4 × hole for M12 4 × hole for M12 4 × hole for M12 4 × hole for M12

• Conductor cross section, max. (IEC) mm2 Busbar Busbar Busbar Busbar

PE1/GND connection M12 screw M12 screw M12 screw M12 screw

• Conductor cross section, max. (IEC) mm2 240 240 240 240

PE2/GND connection 2 × M12 screw 3 × M12 screw 3 × M12 screw 3 × M12 screw

• Conductor cross section, max. (IEC) mm2 2 x 240 3 x 240 3 x 240 3 x 240

Cable length, max. 4)

• Shielded m (ft) 2250 (7382) 2250 (7382) 2250 (7382) 2250 (7382)

• Unshielded m (ft) 3375 (11073) 3375 (11073) 3375 (11073) 3375 (11073)

Degree of protection IP00 IP00 IP00 IP00

Dimensions

• Width mm (in) 503 (19.8) 704 (27.7) 704 (27.7) 704 (27.7)

• Height mm (in) 1475 (58.1) 1480 (58.3) 1480 (58.3) 1480 (58.3)

• Depth mm (in) 540 (21.3) 550 (21.6) 550 (21.6) 550 (21.6)

Weight, approx. kg (lb) 290 (639) 450 (992) 450 (992) 450 (992)

Frame size HX JX JX JX

Minimum short-circuit current5) A 8400 10500 16000 20000

1) The base-load current IH DC is the basis for a duty cycle of 150 % for 60 s 4) Total of all motor cables and DC link. Longer cable lengths for specific

Air-cooled Active Interface Modules in chassis format

7

Overview

Active Interface Modules are used in conjunction with Active Line Modules. Active Interface Modules contain a Clean Power Filter with basic RI suppression, the pre-charging circuit for the Active Line Module, the line voltage sensing circuit and monitor-ing sensors. The bypass contactor is an integral component in types FI and GI. This ensures a highly compact design. The bypass contactor must be provided separately for frame sizes HI and JI.

Line harmonics are largely suppressed by the Clean Power Filter.

Design

Active Interface Modules have the following interfaces as standard:

• 1 line supply connection

• 1 load connection

• 1 connection for the 24 V DC electronics power supply

• 1 connection for the external 230 V AC supply (fan power supply)

• 1 DRIVE-CLiQ socket (on VSM10 Voltage Sensing Module)

• 1 connection for pre-charging circuit, frame sizes HI and JI

• 1 PE connection

The scope of supply of the Active Interface Modules includes:

• DRIVE-CLiQ cable for the connection between Active Interface Module and Active Line Module

• 1 set of warning labels in 30 languages

(BG, CN, CZ, DE, DK, EE, ES, FI, FR, GB, GR, HU, IE, IS, IT, JP, KR, LT, LV, MT, NL, NO, PL, PT, RO, RU, SE, SI, SK, TR)

Selection and ordering data Suitable for

Active Line Module chassis format, air-cooled

Rated power of the Active Line Modules at 400 V, 50 Hz (460 V, 60 Hz) or 690 V, 50 Hz (575 V, 60 Hz)

Active Interface Module

kW (hp) Article No.

Line voltage 380 ... 480 V 3 AC

6SL3330-7TE32-1AA3 132 (200) 6SL3300-7TE32-6AA0 6SL3330-7TE32-6AA3 160 (250) 6SL3300-7TE32-6AA0 6SL3330-7TE33-8AA3 235 (400) 6SL3300-7TE33-8AA0 6SL3330-7TE35-0AA3 300 (500) 6SL3300-7TE35-0AA0 6SL3330-7TE36-1AA3 380 (600) 6SL3300-7TE38-4AA0 6SL3330-7TE37-5AA3 450 (600) 6SL3300-7TE38-4AA0 6SL3330-7TE38-4AA3 500 (700) 6SL3300-7TE38-4AA0 6SL3330-7TE41-0AA3 630 (900) 6SL3300-7TE41-4AA0 6SL3330-7TE41-2AA3 800 (1000) 6SL3300-7TE41-4AA0 6SL3330-7TE41-4AA3 900 (1250) 6SL3300-7TE41-4AA0 Line voltage 500 ... 690 V 3 AC

6SL3330-7TG35-8AA3 630 (675) 6SL3300-7TG35-8AA0 6SL3330-7TG37-4AA3 800 (900) 6SL3300-7TG37-4AA0 6SL3330-7TG41-0AA3 1100 (1250) 6SL3300-7TG41-3AA0 6SL3330-7TG41-3AA3 1400 (1600) 6SL3300-7TG41-3AA0

Air-cooled Active Interface Modules in chassis format

7

Integration

Connection example of an Active Interface Module with integrated bypass contactor (frame sizes FI and GI)

to Active Line