Power Module Chassis

format

Option

Braking module

DRIVE-CLiQ socket 0

DRIVE-CLiQ socket 1

DRIVE-CLiQ socket 2

DRIVE-CLiQ 1) 24 V supply cable to power a CU310-2 or D410-2

Control Unit built into the Power Module

IPD card Control Unit

-Temp

Air-cooled Power Modules in chassis format

7

Technical specifications General technical specifications

Electrical specifications Line connection voltage

Up to 2000 m (6562 ft) above sea level

380 ... 480 V 3 AC ±10 % (-15 % <1 min)

Line power factor

for a 3 AC line supply voltage and output power

• Basic fundamental (cosϕ1) >0.96

• Total (λ) 0.75 ... 0.93

DC link voltage, approx. 1) 1.35 × line voltage Output voltage, approx. 0.97 x Uline Output frequency 2)

• Control mode Servo 0 ... 550 Hz

• Control mode Vector 0 ... 550 Hz

• Control mode V/f 0 ... 550 Hz

Main contactor control

• Terminal block -X9/5-6 240 V AC, max. 8 A 30 V DC, max. 1 A

Safety Integrated Safety Integrity Level 2 (SIL2) acc. to IEC 61508, Performance Level d (PLd) acc. to EN ISO 13849-1 and Control Category 3 acc. to EN ISO 13849-1.

1) The DC link voltage is unregulated and load-dependent.

For additional information, please refer to the SINAMICS Low Voltage Engineering Manual.

2) Please note:

• Note the correlation between max. output frequency, pulse frequency and current derating. Higher output frequencies on request.

For further information, see

Air-cooled Power Modules in chassis format

7

Technical specifications (continued)

Line voltage 380 ... 480 V 3 AC Power Modules

• Rated input current Irated I A 229 284 338 395 509

• Maximum input current Imax I A 335 410 495 606 781

Current demand

• 24 V DC auxiliary power supply A 0.8 0.8 0.9 0.9 0.9

Pulse frequency 5)

• Rated frequency kHz 2 2 2 2 2

• Pulse frequency, max.

- Without current derating kHz 2 2 2 2 2

- With current derating kHz 8 8 8 8 8

Power loss, max. 6)

• At 50 Hz 400 V kW 2.46 3.27 4 4.54 5.78

• At 60 Hz 460 V kW 2.54 3.36 4.07 4.67 5.96

Cooling air requirement m3/s (ft3/s) 0.17 (6.0) 0.23 (8.1) 0.36 (12.7) 0.36 (12.7) 0.36 (12.7) Sound pressure level LpA

(1 m) at 50/60 Hz

dB 66/67 71/71 68/72 68/72 68/72

Line connection U1, V1, W1

Flat connector for M10 screw

Flat connector for M10 screw

Flat connector for M10 screw

Flat connector for M10 screw

Flat connector for M10 screw

• Conductor cross section, max. (IEC) mm2 2 × 185 2 × 185 2 × 240 2 × 240 2 × 240

Motor connection U2/T1, V2/T2, W2/T3

Flat connector for M10 screw

Flat connector for M10 screw

Flat connector for M10 screw

Flat connector for M10 screw

Flat connector for M10 screw

• Conductor cross section, max. (IEC) mm2 2 × 185 2 × 185 2 × 240 2 × 240 2 × 240

Cable length, max. 7)

• Shielded m (ft) 300 (984) 300 (984) 300 (984) 300 (984) 300 (984)

• Unshielded m (ft) 450 (1476) 450 (1476) 450 (1476) 450 (1476) 450 (1476)

PE1/GND connection Flat connector for

M10 screw

Flat connector for M10 screw

Flat connector for M10 screw

Flat connector for M10 screw

Flat connector for M10 screw

• Conductor cross section, max. (IEC) mm2 2 × 185 2 × 185 2 × 240 2 × 240 2 × 240

PE2/GND connection M10 screw M10 screw M10 screw M10 screw M10 screw

• Conductor cross section, max. (IEC) mm2 2 × 185 2 × 185 2 × 240 2 × 240 2 × 240

Degree of protection IP20 IP20 IP20 IP20 IP20

Dimensions

• Width mm (in) 326 (12.8) 326 (12.8) 326 (12.8) 326 (12.8) 326 (12.8)

• Height mm (in) 1400 (55.1) 1400 (55.1) 1533 (60.3) 1533 (60.3) 1533 (60.3)

• Depth mm (in) 356 (14.0) 8) 356 (14.0) 8) 549 (21.6) 549 (21.6) 549 (21.6)

Weight, approx. kg (lb) 104 (229) 104 (229) 162 (357) 162 (357) 162 (357)

Frame size FX FX GX GX GX

Minimum short-circuit current9) A 3000 3600 4400 4400 8000

1) Rated output of a typical 6-pole standard induction motor based on IL or IH for 400 V 3 AC 50 Hz.

2) Rated output of a typical 6-pole standard induction motor based on IL or IH for 460 V 3 AC 60 Hz.

3) The base-load current IL is based on a duty cycle of 110 % for 60 s or 150 % for 10 s with a duty cycle duration of 300 s.

4) The base-load current IH is based on a duty cycle of 150 % for 60 s or 160 % for 10 s with a duty cycle duration of 300 s.

5) Information regarding the correlation between the pulse frequency and

6) The specified power loss represents the maximum value at 100 % utilization.

The value is lower under normal operating conditions.

7) Longer cable lengths for specific configurations are available on request.

For additional information, please refer to the SINAMICS Low Voltage Engineering Manual.

8) Depth = 421 mm (16.6 in) including front cover when CU310-2 Control Unit is installed.

9) Current required for reliably triggering protective devices.

Air-cooled Active Line Modules in chassis format

7

Overview

The self-commutated infeed/regenerative feedback units with IGBTs generate a regulated DC link voltage. This means that the connected Motor Modules are decoupled from the line voltage.

Line voltage fluctuations within the permissible supply toler-ances have no effect on the motor voltage.

If required, the Active Line Modules can also provide reactive power compensation.

Active Line Modules are designed for connection to grounded TN/TT and non-grounded IT supply systems.

Active Line Modules are always operated together with the as-sociated Active Interface Modules. These include the necessary pre-charging circuit as well as a Clean Power Filter.

Design

The Active Line Modules have the following interfaces as standard:

• 1 line supply connection

• 1 connection for the 24 V DC electronics power supply

• 1 DC link connection (DCP, DCN) for supplying the connected Motor Modules

• 1 DC link connection (DCPA, DCNA) for connecting a Braking Module

• 3 DRIVE-CLiQ sockets

• 1 temperature sensor input for KTY84-130, Pt1000, PTC or Pt100 (Pt1000 can be used from firmware V4.7 HF17)

• 2 PE connections

The status of the Active Line Modules is indicated via three LEDs.

The scope of supply of the Active Line Modules includes:

• DRIVE-CLiQ cable to connect to a Control Unit

• DRIVE-CLiQ cable to connect the Control Unit to the first Motor Module

• 1 set of warning labels in 30 languages

(BG, CN, CZ, DE, DK, EE, ES, FI, FR, GB, GR, HU, IE, IS, IT, JP, KR, LT, LV, MT, NL, NO, PL, PT, RO, RU, SE, SI, SK, TR)

Selection and ordering data Rated power

at 400 V, 50 Hz (460 V, 60 Hz) or 690 V, 50 Hz (575 V, 60 Hz)

Rated infeed/

regenerative feedback current

Active Line Module

kW (hp) A Article No.

Line voltage 380 ... 480 V 3 AC

132 (200) 210 6SL3330-7TE32-1AA3

160 (250) 260 6SL3330-7TE32-6AA3

235 (400) 380 6SL3330-7TE33-8AA3

300 (500) 490 6SL3330-7TE35-0AA3

380 (600) 605 6SL3330-7TE36-1AA3

450 (600) 745 6SL3330-7TE37-5AA3

500 (700) 840 6SL3330-7TE38-4AA3

630 (900) 985 6SL3330-7TE41-0AA3

800 (1000) 1260 6SL3330-7TE41-2AA3

900 (1250) 1405 6SL3330-7TE41-4AA3

Line voltage 500 ... 690 V 3 AC

630 (675) 575 6SL3330-7TG35-8AA3

800 (900) 735 6SL3330-7TG37-4AA3

1100 (1250) 1025 6SL3330-7TG41-0AA3

1400 (1600) 1270 6SL3330-7TG41-3AA3

Description Article No.

Accessories

Dust protection blanking plugs (50 units)

For DRIVE-CLiQ port

6SL3066-4CA00-0AA0

Air-cooled Active Line Modules in chassis format

7

Integration

The Active Line Modules communicate with the higher-level control module via DRIVE-CLiQ. The control module in this case can be a CU320-2 or a SIMOTION D Control Unit. An external 24 V DC power supply is required to operate the Active Line Modules.

Connection example of an Active Line Module

Technical specifications General technical specifications

P24 V EP +24 V

ext.

24 V DC

Activation of

buffer protection Internal power supply to Active Interface Module

from Active Interface Module Fan supply terminal for sizes HX and JX.

The number of the fans depends on the frame size.

Connection for Braking Module Fan

internal Fan

Fan supply terminal for sizes FX and GX directly on the fuse carrier.

internal Fan

DC link connection

G_D211_EN_00258a

Active Line